| 2019-05-28 06:35:58 | 1.) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, THE SPECS FOR THE RANGE ARE PARTIAL AND DO |
| | NOT SHOW THE EQUIPMENT IS LISTED AND LABELED. |
| | 2) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN / FLOOR PLAN |
| | CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATERS |
| | ARE INSIDE OR OUTSIDE.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | APPLIANCES. 2017 FBC-FUEL GAS SEC. 304.1. WHERE |
| | COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS |
| | SEC.304.9.3. |
| | 5) EACH OF THE APPLIANCES SERVED SHALL BE INTERLOCKED |
| | WITH THE MECHANICAL AIR SUPPLY SYSTEM TO PREVENT MAIN |
| | BURNER OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM |
| | IS NOT IN OPERATION. 2017 FBC-FUEL GAS SEC.304.9.2. |
| | 6) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| | 2017 FBC-FUEL GAS SECS. 502 THRU 505 ( IF APPLICABLE). |
| | 7) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE |
| | BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| | UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| | SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1 OF NFPA 96-14. |
| | 8) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| | REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| | BEING ADDED TO THE EXISTING HOT WATER SYSTEM? WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 9) PUT THE NAME OF THIS BUSINESS ON THE PERMIT |
| | APPLICATIONS. CITY RECORDS DO NOT CURRENTLY SHOW ANY |
| | PREVIOUS PERMITS FOR THIS SPACE OR ANY BUSINESS TAX |
| | RECEIPT FOR ANY PREVIOUS BUSINESS AT THIS UNIT ADDRESS. |
| | IS THIS A CHANGE OF OCCUPANCY PER THE 2017 FBC-EXISTING |
| | BUILDING CODE CHAPTER 10? WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 10) LIST THE LAST PREVIOUS BUSINESS AND OCCUPANCY TYPE |
| | THAT WAS LOCATED IN THIS SPACE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |