Plan Review Notes
Plan Review Notes For Permit 19051045
Permit Number 19051045
Review Stop P
Sequence Number 5
Notes
Date Text
2020-04-07 12:14:53REVIEWED BY JERRY SMITH, ENTERED BY JOHN PEARSON:
  
 PLUMBING COMMENTS: APPROVED W/PROVISO
  
 1. THE SANITARY LINE THAT THE PUMP IS DISCHARGING TO
 APPARENTLY HAS BEEN ABANDONED AND IS CAPPED OFF PER A
 WPB FIELD INSPECTOR AND REINFORCED BY NOTE ON PLAN
 SHEET C7 ?EXISTING SANITARY SERVICE TO BE REMOVED. CUT
 AND CAP AT SERVICE WYE?. RESEARCH SHALL BE DONE AND
 PROVIDE AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB
 FBC 107.2.1 AND WPB FBC 107.3.4.1, DOCUMENTATION AND
 VERIFICATION BY THE DESIGN PROFESSIONAL AND CONTRACTOR
 THAT THIS LINE IS STILL ACTIVE. SUBMITTAL SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO INSPECTION.
 PROCEED AT YOUR OWN RISK.
 2. REGARDING THE AAV SERVICING THE DECK DRAIN (SEE PLAN
 SHEET P101; KEYNOTE 7), FBC PL 904.1 REQUIRES THAT EACH
 BUILDING DRAIN SHALL HAVE NOT LESS THAN ONE (1) VENT
 PIPE THAT EXTENDS TO THE OUTDOORS. PER FBC 107.2.1,
 PROVIDE DOCUMENTATION AND VERIFICATION THAT THERE IS AN
 EXISTING VENT TO THE OUTDOORS THAT SERVICES THE
 BUILDING DRAIN OR PROVIDE IN A REVISION A VENT THAT
 COMPLIES. SAID DOCUMENTATION/VERIFICATION SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO INSPECTION.
 PROCEED AT YOUR OWN RISK.
 3. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER