Plan Review Notes
Plan Review Notes For Permit 19051045
Permit Number 19051045
Review Stop P
Sequence Number 2
Notes
Date Text
2019-12-10 17:39:05PLUMBING 2ND REVIEW**DENIED**19051045
 1) PROVIDE A ISOMETRIC DRAWING OF THE STORM SYSTEM.
 SHT. P101 DOES NOT SHOW THIS. IF THIS NEW SYSTEM IN
 ANYWAY CONNECTS INTO THE EXISTING SYSTEM YOU MUST ALSO
 PROVIDE THAT INFORMATION VERIFYING PIPE SIZE IS LARGE
 ENOUGH TO HANDLE THE NEW LOAD. FBC 107.3.5
 2) PLEASE CHANGE THE WORDING BACKFLOW DEVICE TO CHECK
 VALVE FOR THE SUMP PUMP AND CORRECT THE FOLLOWING.
  
 A) FBC-PLB712.2 VALVES REQUIRED: A CHECK VALVE AND A
 FULL OPEN VALVE LOCATED ON THE DISCHARGE SIDE OF THE
 CHECK VALVE SHALL BE INSTALLED IN THE PUMP OR EJECTOR
 DISCHARGE PIPING BETWEEN THE PUMP OR EJECTOR AND THE
 GRAVITY DRAINAGE SYSTEM. ACCESS SHALL BE PROVIDED TO
 SUCH VALVES. SUCH VALVES SHALL BE LOCATED ABOVE THE
 SUMP COVER REQUIRED BY SECTION 712.1 OR, WHERE THE
 DISCHARGE PIPE FROM THE EJECTOR IS BELOW GRADE, THE
 VALVES SHALL BE ACCESSIBLY LOCATED OUTSIDE THE SUMP
 BELOW GRADE IN AN ACCESS PIT WITH A REMOVABLE ACCESS
 COVER.
 B) DISCHARGE NOT PERMITTED TO GO INTO THE STORM.
 FBC-PLB 712.3.5. PUMP CONNECTION TO THE DRAINAGE
 SYSTEM. PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL
 CONNECT TO A BUILDING SEWER, BUILDING DRAIN, SOIL
 STACK, WASTE STACK OR HORIZONTAL BRANCH DRAIN. WHERE
 THE DISCHARGE LINE CONNECTS INTO HORIZONTAL DRAINAGE
 PIPING, THE CONNECTION SHALL BE MADE THROUGH A WYE
 FITTING INTO THE TOP OF THE DRAINAGE PIPING AND SUCH
 WYE FITTING SHALL BE LOCATED NOT LESS THAN 10 PIPE
 DIAMETERS FROM THE BASE OF ANY SOIL STACK, WASTE STACK
 OR FIXTURE DRAIN. PROVIDE ISOMETRIC DRAWING SHOWING
 CONNECTING INTO THE SANITARY SYSTEM. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  
  
  