| 2019-12-10 17:39:05 | PLUMBING 2ND REVIEW**DENIED**19051045 |
| | 1) PROVIDE A ISOMETRIC DRAWING OF THE STORM SYSTEM. |
| | SHT. P101 DOES NOT SHOW THIS. IF THIS NEW SYSTEM IN |
| | ANYWAY CONNECTS INTO THE EXISTING SYSTEM YOU MUST ALSO |
| | PROVIDE THAT INFORMATION VERIFYING PIPE SIZE IS LARGE |
| | ENOUGH TO HANDLE THE NEW LOAD. FBC 107.3.5 |
| | 2) PLEASE CHANGE THE WORDING BACKFLOW DEVICE TO CHECK |
| | VALVE FOR THE SUMP PUMP AND CORRECT THE FOLLOWING. |
| | |
| | A) FBC-PLB712.2 VALVES REQUIRED: A CHECK VALVE AND A |
| | FULL OPEN VALVE LOCATED ON THE DISCHARGE SIDE OF THE |
| | CHECK VALVE SHALL BE INSTALLED IN THE PUMP OR EJECTOR |
| | DISCHARGE PIPING BETWEEN THE PUMP OR EJECTOR AND THE |
| | GRAVITY DRAINAGE SYSTEM. ACCESS SHALL BE PROVIDED TO |
| | SUCH VALVES. SUCH VALVES SHALL BE LOCATED ABOVE THE |
| | SUMP COVER REQUIRED BY SECTION 712.1 OR, WHERE THE |
| | DISCHARGE PIPE FROM THE EJECTOR IS BELOW GRADE, THE |
| | VALVES SHALL BE ACCESSIBLY LOCATED OUTSIDE THE SUMP |
| | BELOW GRADE IN AN ACCESS PIT WITH A REMOVABLE ACCESS |
| | COVER. |
| | B) DISCHARGE NOT PERMITTED TO GO INTO THE STORM. |
| | FBC-PLB 712.3.5. PUMP CONNECTION TO THE DRAINAGE |
| | SYSTEM. PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL |
| | CONNECT TO A BUILDING SEWER, BUILDING DRAIN, SOIL |
| | STACK, WASTE STACK OR HORIZONTAL BRANCH DRAIN. WHERE |
| | THE DISCHARGE LINE CONNECTS INTO HORIZONTAL DRAINAGE |
| | PIPING, THE CONNECTION SHALL BE MADE THROUGH A WYE |
| | FITTING INTO THE TOP OF THE DRAINAGE PIPING AND SUCH |
| | WYE FITTING SHALL BE LOCATED NOT LESS THAN 10 PIPE |
| | DIAMETERS FROM THE BASE OF ANY SOIL STACK, WASTE STACK |
| | OR FIXTURE DRAIN. PROVIDE ISOMETRIC DRAWING SHOWING |
| | CONNECTING INTO THE SANITARY SYSTEM. FBC 107.3.5 |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | 561-248-2703 |
| | |
| | |
| | |