2019-08-26 07:26:18PLUMBING 1ST REVIEW**DENIED
 ***SEPARATE PLUMBING, GAS, AND BACKFLOW PERMITS ARE
 REQUIRED***
  
 1-SHT. G104 SHOWS BATHROOM DETAILS TO INCLUDE
 ACCESSIBLE BUT YOUR PLAN LACKS ANY TOILET ROOMS. PLEASE
 CLARIFY.
 2- SHT. G104 CALLS OUT GRAB BAR MEASUREMENT 36? TO THE
 CENTER OF THE BAR. THE CORRECT MEASUREMENT IS 33?-36?
 TO THE TOP GRIPPING SURFACE. PLEASE CORRECT FBC-ACC
 609.4
 3-PROVIDE A ISOMETRIC DRAWING OF THE COMPLETE STORM
 SYSTEM. FBC 107.3.5
 4) PROVIDE SUMP PUMP DETAIL AND LOCATION OF INDIRECT
 DRAIN. FBC 107.2.1
 5) PROVIDE ROOF DRAIN MANUFACTURES INSTALLATION MANUAL
 SHOWING RATE OF GPM.
  