| 2019-08-16 07:56:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19051045 |
| | 8/16/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) NO MECHANICAL SHEETS WERE UPLOADED FOR REVIEW. |
| | PLEASE SEE THE INDEX ON G102 SHOWING MECHANICAL SHEETS |
| | AND CLARIFY IF MECHANICAL IS REQUIRED FOR THIS PHASE OF |
| | THE PROJECT. IF NOT, CORRECT THE INDEX SO IT CORRELATES |
| | WITH THE PLANS, AND NOTE ON THE PLANS THAT A SEPARATE |
| | MECHANICAL PERMIT WILL BE REQUIRED- SECTION 107.2.1 |
| | WPB. |
| | PLEASE NOTE THAT ENCLOSED PARKING GARAGES REQUIRE |
| | MECHANICAL EXHAUST VENTILATION SYSTEMS DESIGNED IN |
| | ACCORDANCE WITH SECTION 404 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |