| Plan Review Notes For Permit 19051034 |
| Permit Number |
19051034 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-10 09:07:55 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 19051034 | | | REVIEWED: JUNE 10, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | | | | 107.5.3 FBC(B) THE DESIGN CALCULATIONS PROVIDED ARE | | | BASED ON WIND SPEED OF 115, BUT THE OTHER DRAWINGS | | | SHEETS STATES 175 MPH BEING USED. | | | PLEASE COORDINATE WIND SPEEDS. | | | TYPICALLY WE USE 170 VULT AND 132 ASD FOR THIS AREA. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | |
|