2022-01-06 16:38:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL X IS A 3 PHASE DELTA CONNECTED PANEL "B" PHASE IS
 A HIGH LEG.
  
 PANELS "A"M AND "B" AND CIRCUITS 15 AND 19 ARE
 CONNECTED TO THIS LEG PER PANEL SCHEDULES. PLEASE FIX.
  
 PLEASE SHOW LISTING FOR BAPTISIAML EQUIPMENT FOR USE AS
 HYDROMASAGE TUB OR EQUAL. 110.3