| Plan Review Notes For Permit 19050991 |
| Permit Number |
19050991 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-01-06 16:38:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PANEL X IS A 3 PHASE DELTA CONNECTED PANEL "B" PHASE IS | | | A HIGH LEG. | | | | | | PANELS "A"M AND "B" AND CIRCUITS 15 AND 19 ARE | | | CONNECTED TO THIS LEG PER PANEL SCHEDULES. PLEASE FIX. | | | | | | PLEASE SHOW LISTING FOR BAPTISIAML EQUIPMENT FOR USE AS | | | HYDROMASAGE TUB OR EQUAL. 110.3 |
|