| 2019-07-01 14:38:17 | 1ST REVIEW: 19050991 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. GRAB BARS REQUIRED IN AMBULATORY STALLS PER FBC ACC |
| | 604.8.2.3 |
| | |
| | 2. SHT. A-1 NOTE #20 THE WALLS AROUND THE URINALS AND |
| | TOILETS SHALL BE WATER PROOF AND COMPLY WITH PER FNBC |
| | PL BG] 419.3 FBC 1210.2.2 |
| | |
| | 3. THE EXISTING MENS TOILET SHOULD BE 16"- 18" OFF SIDE |
| | WALL TO COMPLY WITH FBC ACC 604.2 |
| | |
| | 4. SHT. P-2 THE FOLLOWING CHANGES NEED TO THE SANITARY |
| | ISOMETRIC TO COMPLY WITH FBC PL |
| | A) THE TOILET IN THE WOMENS BATHROOM THAT IS IN THE |
| | CORNER BY ITSELF IS NOT VENTED PROPERLY IT SHALL BE |
| | VENTED BEFORE CONNECTING TO THE BUILDING DRAIN. PER FBC |
| | PL 901.2.1 |
| | B)THE HORIZONTAL DRY VENT AT THE END OF THE RUN IS |
| | PROHIBITED PLEASE REMOVE .PER FBC PL 905.3 |
| | |
| | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 6. A VALVE IS REQUIRED ON ALL DROPS ON THE WATER |
| | SYSTEM. PER FBC PL 606.1(5) |
| | |
| | 7.PLACE NOTE ON PLAN A SEPARATE PERMIT IS REQUIRED FOR |
| | THE BACKFLOW ON THE BAPTISTRY PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| 2019-06-26 12:14:03 | GPJ TO DO REVIEW. |