| 2019-07-09 14:56:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19050991 |
| | 7/9/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) M-1: THE AMOUNT OF RETURN AIR TAKEN FROM THE NARTHEX |
| | SHALL BE NOT GREATER THAN THE FLOW RATE OF SUPPLY AIR |
| | DELIVERED TO THE SPACE- SECION 601.5(3) FBC M. |
| | |
| | 3) A-1 & M-1: IS THE AIR HANDLER ENCLOSED IN A CLOSET |
| | OR NOT?- SECTION 107.2.1 WPB. |
| | |
| | 4) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION |
| | 370.2.1 FBC M. |
| | |
| | 5) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR |
| | THE LOUVER- RULE 9N-3 FAC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |