Plan Review Notes
Plan Review Notes For Permit 19050991
Permit Number 19050991
Review Stop M
Sequence Number 1
Notes
Date Text
2019-07-09 14:56:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050991
 7/9/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) M-1: THE AMOUNT OF RETURN AIR TAKEN FROM THE NARTHEX
 SHALL BE NOT GREATER THAN THE FLOW RATE OF SUPPLY AIR
 DELIVERED TO THE SPACE- SECION 601.5(3) FBC M.
  
 3) A-1 & M-1: IS THE AIR HANDLER ENCLOSED IN A CLOSET
 OR NOT?- SECTION 107.2.1 WPB.
  
 4) M-1: PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION
 370.2.1 FBC M.
  
 5) SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR
 THE LOUVER- RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  