| Plan Review Notes For Permit 19050991 |
| Permit Number |
19050991 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-07-02 11:30:12 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1 | | | | | | SYMBOL SPL ? | | | | | | PAGE E-2 | | | | | | PANEL "X" CIRCUIT #19 ON HI LEG | | | PANEL "A" "B" PHASE ON HI LEG ONLY HAS A AND B PHASES | | | 120 VOLT CIRCUIT WILL NOT WORK. | | | BAPISTRY HEATER TO BE GFCI PROTECTED 680.71 OR 680.61 | | | LOW VOLTAGE PANEL ? WHAT IS IT FOR? | | | PANELS A AND B NEED TO SHOW WIRE SIZES. 215.5 |
|