Plan Review Notes
Plan Review Notes For Permit 19050991
Permit Number 19050991
Review Stop E
Sequence Number 1
Notes
Date Text
2019-07-02 11:30:12FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 SYMBOL SPL ?
  
 PAGE E-2
  
 PANEL "X" CIRCUIT #19 ON HI LEG
 PANEL "A" "B" PHASE ON HI LEG ONLY HAS A AND B PHASES
 120 VOLT CIRCUIT WILL NOT WORK.
 BAPISTRY HEATER TO BE GFCI PROTECTED 680.71 OR 680.61
 LOW VOLTAGE PANEL ? WHAT IS IT FOR?
 PANELS A AND B NEED TO SHOW WIRE SIZES. 215.5