2019-07-03 10:37:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050991
 ADD: 2015 PARKER AVE.
 CONT: K & M COMMERCIAL CONSTRUCTION LLC
 TEL: 561-383-2817
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 03/2019
 ACTION: DENIED
  
 1) PLEASE NOTE PALM BEACH COUNTY GEO NAV MAPPING AS
 WELL AS THE SUBMITTED SURVEY INDICATE THE EXISTING
 BUILDING IS LOCATED IN AN AE FLOOD ZONE AND REQUIRED
 BASE FLOOD ELEVATION OF 12.1 FEET NAVD 88.
 OCT. 11/2017 THE CITY ADOPTED AN ADDITIONAL ONE FOOT OF
 FREE BOARD WHICH WILL BE REQUIRED OR (2) FEET ABOVE
 BASE FLOOD ELEVATION. THE NEW LOWEST PART OF ANY FLOOR
 WITHIN THE EXISTING BUILDING AND ADDITION WILL NEED TO
 BE 14.1 FEET NAVD 88.
  
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR
 FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR,
 RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE
 CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT
 OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF
 NEW CONSTRUCTION.
  
 THE PROPOSED IMPROVEMENT ($843,160.00 DOLLARS) APPEARS
 TO BE A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH
 COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE
 STRUCTURE ($532,621.00). THIS IS A SUBSTANTIAL
 IMPROVEMENT. THE EXISTING STRUCTURE IS TO BE BROUGHT
 INTO COMPLIANCE (BFE 14.1? NAVD88 FOR THE LOWEST
 FINISHED FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT
 CAN PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE
 PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL
 BULLETIN 758 SECTION 4.5:
 HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2
 5045-2915/P_758_COMPLETE_R3.PDF
  
 THE ORIGINAL BUILDING WAS BUILT IN 1956 AND IS
 PRE-FIRM. WE HAVE LOOKED THROUGH THE SUBSTANTIAL
 IMPROVEMENT/ SUBSTANTIAL DAMAGE DESK REFERENCE FEMA
 P-758 / MAY 2010 TABLE 6-1A. COMPLIANCE MATRIX (A
 ZONES). WITH THE LATERAL ADDITION AND THE RENOVATION OF
 THE EXISTING BUILDING BEING A SUBSTANTIAL IMPROVEMENT
 BOTH THE ADDITION AND THE EXISTING BUILDING WILL NEED
 TO COMPLY WITH THE PROVISIONS OF SECTION 1612 FLOOD
 LOADS OF THE 2017FBC-B. PLEASE NOTE ASCE 7 AND WITH
 ASCE 24 ARE BOTH BOOKLETS THAT ARE ADDRESSED BY CODE
 SECTION 1612.4. PLEASE ALSO NOTE THERE IS AN OPTION TO
 DRY FLOOD PROOF THE BUILDING. YOU MAY ALSO WANT TO
 REVIEW THE FEMA BOOKLET: FLOODPROOFING NON-RESIDENTIAL
 BUILDINGS.
 PLEASE SHOW HOW COMPLIANCE WITH 1612.5 FLOOD HAZARD
 DOCUMENTATION WILL BE ACHIEVED.
  
 2017 FBC-B SECTION 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
  
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING THE
 BASEMENT, AS REQUIRED BY THE LOWEST FLOOR ELEVATION
 INSPECTION IN SECTION 110.3, BUILDING, 1.1 AND FOR THE
 FINAL INSPECTION IN SECTION 110.3, BUILDING, 5.1.
  
 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE
 24.
  
 1.3. FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
 2. FOR CONSTRUCTION IN COASTAL HIGH HAZARD AREAS AND
 COASTAL A ZONES:
  
 2.1.THE ELEVATION OF THE BOTTOM OF THE LOWEST
 HORIZONTAL STRUCTURAL MEMBER AS REQUIRED BY THE LOWEST
 FLOOR ELEVATION INSPECTION IN SECTION 110.3, BUILDING,
 1.1 AND FOR THE FINAL INSPECTION IN SECTION 110.3,
 BUILDING, 5.1.
  
 2.2. CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT
 THAT THE BUILDING IS DESIGNED IN ACCORDANCE WITH ASCE
 24, INCLUDING THAT THE PILE OR COLUMN FOUNDATION AND
 BUILDING OR STRUCTURE TO BE ATTACHED THERETO IS
 DESIGNED TO BE ANCHORED TO RESIST FLOTATION, COLLAPSE
 AND LATERAL MOVEMENT DUE TO THE EFFECTS OF WIND AND
 FLOOD LOADS ACTING SIMULTANEOUSLY ON ALL BUILDING
 COMPONENTS, AND OTHER LOAD REQUIREMENTS OF CHAPTER 16.
  
 2.3. FOR BREAKAWAY WALLS DESIGNED TO HAVE A RESISTANCE
 OF MORE THAN 20 PSF DETERMINED USING ALLOWABLE STRESS
 DESIGN, CONSTRUCTION DOCUMENTS SHALL INCLUDE A
 STATEMENT THAT THE BREAKAWAY WALL IS DESIGNED IN
 ACCORDANCE WITH ASCE 24.
  
  
 ***********************
  
 2) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD
 BUILDING. THRESHOLD BUILDING / FL S. S. 553.71(7)
 ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3. ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) 014-LS1-LIFE SAFETY PLAN:
  
 3A) UNDER THE HEADING OF PROJECT DATA THE CONSTRUCTION
 TYPE IS LISTED AS TYPE 5B UNSPRINKLERED, UNPROTECTED.
 WITH A TOTAL AREA WITH NEW ADDITION AND MEZZANINE OF
 6,569 SQ. FT. WE GOT AN AREA OF 6,812 SQ. FT. WITH THE
 PROPOSED NEW COVERED ENTRY.
  
 THERE IS A QUESTION AS TO THE BUILDING DIRECTLY BEHIND
 THE SANCTUARY. THIS BUILDING IS 12.7 X 39 SQ. FT. OR
 495.3 SQ. FT. THE SITE PLAN INDICATES THERE IS ONLY 3
 FEET BETWEEN THE BUILDINGS. HOW IS THE SQUARE FEET
 FIGURED, AS 2 BUILDINGS WITH AN ASSUMED PROPERTY LINE
 AND RATED WALLS OR AS ONE BUILDING? THE AGGREGATE AREA
 OF BOTH BUILDINGS BEING COMBINED INTO ONE AGGREGATE
 BUILDING AREA AND COMPLYING WITH THE LIMITATIONS OF 504
 AND 506?
  
 2017 EXIST. BUILDING CODE 1102.2 AREA LIMITATIONS. NO
 ADDITION SHALL INCREASE THE AREA OF AN EXISTING
 BUILDING BEYOND THAT PERMITTED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE,
 BUILDING FOR NEW BUILDINGS UNLESS FIRE SEPARATION AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING IS
 PROVIDED.
  
 PLEASE REVIEW 2017 FBC-B TABLE 506.2 FOR A3 ASSEMBLY
 BUILDINGS TYPE 5-B UNSPRINKLERED ALLOWABLE AREA OF
 6,000 SQ. FT.
  
 2017 EXISTING BUILD. CODE SECTION 1101.2 CREATION OR
 EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE ADDITION IS BEING MADE WITH
 REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING, OR ELECTRICAL SYSTEMS.
  
 3B) UNDER THE HEADING OF PROJECT DATA THE PLANS
 INDICATE AN OCCUPANT LOAD OF 509 OCCUPANTS. PLEASE
 REVIEW SECTION 1102.3 OF THE EXIST. BUILD. CODE SECTION
 1102.3 FIRE PROTECTION SYSTEMS. EXISTING FIRE AREAS
 INCREASED BY THE ADDITION SHALL COMPLY WITH CHAPTER 9
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2017 FBC-B SECTION [F] 903.2.1.3 GROUP A-3. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR FIRE
 AREAS CONTAINING GROUP A-3 OCCUPANCIES AND INTERVENING
 FLOORS OF THE BUILDING WHERE ONE OF THE FOLLOWING
 CONDITIONS EXISTS: 2.THE FIRE AREA HAS AN OCCUPANT LOAD
 OF 300 OR MORE. PLEASE PROVIDE FIRE SPRINKLERS AND
 PLANS FOR THIS BUILDING.
  
 3C) UNDER THE HEADING OF PROJECT DATA THE PLANS
 INDICATE (2) REQUIRED EXITS. PLEASE REVIEW SECTION
 1006.2.1.1 OF THE FBC-B 2017. 1006.2.1.1 THREE OR MORE
 EXITS OR EXIT ACCESS DOORWAYS. THREE EXITS OR EXIT
 ACCESS DOORWAYS SHALL BE PROVIDED FROM ANY SPACE WITH
 AN OCCUPANT LOAD OF 501 TO 1,000. PLEASE CORRECT PLANS.
  
 4) THERE IS A NOTE ON SHEET A1 THAT THE FLOOR SLAB
 SLOPES DOWN +/- 10 INCHES FROM NORTH TO SOUTH. ON
 EITHER THE LIFE SAFETY SHEET OR THE A1 SHEET PLEASE
 PROVIDE WHERE THE FLOOR ELEVATION 100.00 WILL BE. THE 2
 DETAILS SHEET A9 DETAIL A AND SHEET A10 DETAIL E BOTH
 SHOW THE FLOOR ELEVATION AT 100.00. DISCREPANCY IN
 PLANS? IS THE SLOPED FLOOR EXISTING AND BEING DONE AWAY
 WITH? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET S1 THE FOUNDATION PLAN PROVIDES THE FOUNDATION
 IS DESIGNED FOR 2,500 PSF AT 95% COMPACTION, BUT IN
 THIS SUBMITTAL THERE WAS NO SOILS REPORT SUBMITTED,
 THIS IS A QUESTIONABLE AREA WITH A CANAL SO CLOSE. 2017
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6) SHEET S1 HAS THE WIND DESIGN WITH BUILDING RISK
 CATEGORY III AND WIND SPEED (VULT) AS 180 MPH. THE
 PRESSURES GIVEN ARE FOR 50 SQ. FT. EFFECTIVE WIND AREA,
 BUT THE PLAN DOES NOT STATE IF THE PRESSURES ARE GIVEN
 IN VULT OR VASD? SHEET A5 ELEVATIONS PROVIDE PRESSURES
 FOR WALL ZONES 4 & 5 IN VULT , THE VULT PRESSURES ARE
 CORRECT. PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE
 PRODUCT APPROVALS ARE ALSO IN VASD.
 THANK YOU FOR YOUR CO-OPERATION IN THIS MATTER.
  
 7) NEITHER SHEET S1 OR S2 PROVIDE THE PRESSURES +/- FOR
 ROOF ZONES 1, 2 OR 3 THE EFFECTIVE AREA SHOULD BE 10
 SQ. FT. FOR THE ROOFING PRESSURES. 2017 FBC-B 1603.1.4
 WIND DESIGN DATA.
  
 8) THE SUBMITTED PRODUCT APPROVALS DOES NOT HAVE THE
 SHOP DRAWING STAMP OF APPROVALS FROM THE DESIGNER OF
 RECORD. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 11A) PLEASE NOTE THERE WAS A MIAMI-DADE NOA 17-1017.16
 3000 REGISTER ALUMINUM STOREFRONT WINDOW WALL SYSTEM
 SUBMITTED. THIS REPORT EXPIRED ON MARCH 18, 2019.
 REPORT NEEDS UPDATING.
  
 11B THE REGISTER ALUMINUM STOREFRONT WINDOW WALL SYSTEM
 SUBMITTED IS ONLY FOR A WINDOW WALL SYSTEM, IT DOES NOT
 INCLUDE STOREFRONT DOOR SYSTEMS, MULLIONS AND SIDE
 LIGHTS, AND A SEPARATE REPORT IS REQUIRED. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 12) PLEASE NOTE SHEET A1 AT THE SANCTUARY PLATFORM
 INDICATES A NON-COMPLIANT ADA RAMP. THE OCCUPANT LOAD
 FOR THE SANCTUARY PLATFORM IS 96 OCCUPANTS REQUIRING 2
 MEANS OF EGRESS FROM THE PLATFORM. PLEASE SEE IN THE
 2017 FBC-BUILDING SECTION 1012.2 SLOPE. RAMPS USED AS A
 MEANS OF EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER
 THAN ONE UNIT VERTICAL IN 12 UNITS HORIZONTAL (8 %
 SLOPE).
  
 13) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved