| 2019-07-03 10:37:04 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050991 |
| | ADD: 2015 PARKER AVE. |
| | CONT: K & M COMMERCIAL CONSTRUCTION LLC |
| | TEL: 561-383-2817 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 03/2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE PALM BEACH COUNTY GEO NAV MAPPING AS |
| | WELL AS THE SUBMITTED SURVEY INDICATE THE EXISTING |
| | BUILDING IS LOCATED IN AN AE FLOOD ZONE AND REQUIRED |
| | BASE FLOOD ELEVATION OF 12.1 FEET NAVD 88. |
| | OCT. 11/2017 THE CITY ADOPTED AN ADDITIONAL ONE FOOT OF |
| | FREE BOARD WHICH WILL BE REQUIRED OR (2) FEET ABOVE |
| | BASE FLOOD ELEVATION. THE NEW LOWEST PART OF ANY FLOOR |
| | WITHIN THE EXISTING BUILDING AND ADDITION WILL NEED TO |
| | BE 14.1 FEET NAVD 88. |
| | |
| | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & |
| | CONTROL |
| | SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR |
| | FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR, |
| | RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE |
| | CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR |
| | EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT |
| | OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF |
| | NEW CONSTRUCTION. |
| | |
| | THE PROPOSED IMPROVEMENT ($843,160.00 DOLLARS) APPEARS |
| | TO BE A SUBSTANTIAL IMPROVEMENT BASED ON THE PALM BEACH |
| | COUNTY PROPERTY APPRAISERS OFFICE VALUATION FOR THE |
| | STRUCTURE ($532,621.00). THIS IS A SUBSTANTIAL |
| | IMPROVEMENT. THE EXISTING STRUCTURE IS TO BE BROUGHT |
| | INTO COMPLIANCE (BFE 14.1? NAVD88 FOR THE LOWEST |
| | FINISHED FLOOR & ALL MECHANICAL EQUIPMENT). APPLICANT |
| | CAN PROVIDE DOCUMENTATION FOR VALUATION OTHER THAN THE |
| | PROPERTY APPRAISER?S OFFICE; PLEASE SEE FEMA TECHNICAL |
| | BULLETIN 758 SECTION 4.5: |
| | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 |
| | 5045-2915/P_758_COMPLETE_R3.PDF |
| | |
| | THE ORIGINAL BUILDING WAS BUILT IN 1956 AND IS |
| | PRE-FIRM. WE HAVE LOOKED THROUGH THE SUBSTANTIAL |
| | IMPROVEMENT/ SUBSTANTIAL DAMAGE DESK REFERENCE FEMA |
| | P-758 / MAY 2010 TABLE 6-1A. COMPLIANCE MATRIX (A |
| | ZONES). WITH THE LATERAL ADDITION AND THE RENOVATION OF |
| | THE EXISTING BUILDING BEING A SUBSTANTIAL IMPROVEMENT |
| | BOTH THE ADDITION AND THE EXISTING BUILDING WILL NEED |
| | TO COMPLY WITH THE PROVISIONS OF SECTION 1612 FLOOD |
| | LOADS OF THE 2017FBC-B. PLEASE NOTE ASCE 7 AND WITH |
| | ASCE 24 ARE BOTH BOOKLETS THAT ARE ADDRESSED BY CODE |
| | SECTION 1612.4. PLEASE ALSO NOTE THERE IS AN OPTION TO |
| | DRY FLOOD PROOF THE BUILDING. YOU MAY ALSO WANT TO |
| | REVIEW THE FEMA BOOKLET: FLOODPROOFING NON-RESIDENTIAL |
| | BUILDINGS. |
| | PLEASE SHOW HOW COMPLIANCE WITH 1612.5 FLOOD HAZARD |
| | DOCUMENTATION WILL BE ACHIEVED. |
| | |
| | 2017 FBC-B SECTION 1612.5 FLOOD HAZARD DOCUMENTATION. |
| | THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND |
| | SEALED BY A REGISTERED DESIGN PROFESSIONAL AND |
| | SUBMITTED TO THE BUILDING OFFICIAL: |
| | |
| | |
| | 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN |
| | COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES: |
| | |
| | 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING THE |
| | BASEMENT, AS REQUIRED BY THE LOWEST FLOOR ELEVATION |
| | INSPECTION IN SECTION 110.3, BUILDING, 1.1 AND FOR THE |
| | FINAL INSPECTION IN SECTION 110.3, BUILDING, 5.1. |
| | |
| | 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD |
| | ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC |
| | ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM |
| | REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC |
| | FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE |
| | 24. |
| | |
| | 1.3. FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS, |
| | CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT |
| | THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH |
| | ASCE 24. |
| | |
| | 2. FOR CONSTRUCTION IN COASTAL HIGH HAZARD AREAS AND |
| | COASTAL A ZONES: |
| | |
| | 2.1.THE ELEVATION OF THE BOTTOM OF THE LOWEST |
| | HORIZONTAL STRUCTURAL MEMBER AS REQUIRED BY THE LOWEST |
| | FLOOR ELEVATION INSPECTION IN SECTION 110.3, BUILDING, |
| | 1.1 AND FOR THE FINAL INSPECTION IN SECTION 110.3, |
| | BUILDING, 5.1. |
| | |
| | 2.2. CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT |
| | THAT THE BUILDING IS DESIGNED IN ACCORDANCE WITH ASCE |
| | 24, INCLUDING THAT THE PILE OR COLUMN FOUNDATION AND |
| | BUILDING OR STRUCTURE TO BE ATTACHED THERETO IS |
| | DESIGNED TO BE ANCHORED TO RESIST FLOTATION, COLLAPSE |
| | AND LATERAL MOVEMENT DUE TO THE EFFECTS OF WIND AND |
| | FLOOD LOADS ACTING SIMULTANEOUSLY ON ALL BUILDING |
| | COMPONENTS, AND OTHER LOAD REQUIREMENTS OF CHAPTER 16. |
| | |
| | 2.3. FOR BREAKAWAY WALLS DESIGNED TO HAVE A RESISTANCE |
| | OF MORE THAN 20 PSF DETERMINED USING ALLOWABLE STRESS |
| | DESIGN, CONSTRUCTION DOCUMENTS SHALL INCLUDE A |
| | STATEMENT THAT THE BREAKAWAY WALL IS DESIGNED IN |
| | ACCORDANCE WITH ASCE 24. |
| | |
| | |
| | *********************** |
| | |
| | 2) PLEASE NOTE THIS BUILDING QUALIFIES AS A THRESHOLD |
| | BUILDING. THRESHOLD BUILDING / FL S. S. 553.71(7) |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 2G) 110.3.7.4.3. ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 3) 014-LS1-LIFE SAFETY PLAN: |
| | |
| | 3A) UNDER THE HEADING OF PROJECT DATA THE CONSTRUCTION |
| | TYPE IS LISTED AS TYPE 5B UNSPRINKLERED, UNPROTECTED. |
| | WITH A TOTAL AREA WITH NEW ADDITION AND MEZZANINE OF |
| | 6,569 SQ. FT. WE GOT AN AREA OF 6,812 SQ. FT. WITH THE |
| | PROPOSED NEW COVERED ENTRY. |
| | |
| | THERE IS A QUESTION AS TO THE BUILDING DIRECTLY BEHIND |
| | THE SANCTUARY. THIS BUILDING IS 12.7 X 39 SQ. FT. OR |
| | 495.3 SQ. FT. THE SITE PLAN INDICATES THERE IS ONLY 3 |
| | FEET BETWEEN THE BUILDINGS. HOW IS THE SQUARE FEET |
| | FIGURED, AS 2 BUILDINGS WITH AN ASSUMED PROPERTY LINE |
| | AND RATED WALLS OR AS ONE BUILDING? THE AGGREGATE AREA |
| | OF BOTH BUILDINGS BEING COMBINED INTO ONE AGGREGATE |
| | BUILDING AREA AND COMPLYING WITH THE LIMITATIONS OF 504 |
| | AND 506? |
| | |
| | 2017 EXIST. BUILDING CODE 1102.2 AREA LIMITATIONS. NO |
| | ADDITION SHALL INCREASE THE AREA OF AN EXISTING |
| | BUILDING BEYOND THAT PERMITTED UNDER THE APPLICABLE |
| | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE, |
| | BUILDING FOR NEW BUILDINGS UNLESS FIRE SEPARATION AS |
| | REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING IS |
| | PROVIDED. |
| | |
| | PLEASE REVIEW 2017 FBC-B TABLE 506.2 FOR A3 ASSEMBLY |
| | BUILDINGS TYPE 5-B UNSPRINKLERED ALLOWABLE AREA OF |
| | 6,000 SQ. FT. |
| | |
| | 2017 EXISTING BUILD. CODE SECTION 1101.2 CREATION OR |
| | EXTENSION OF NONCONFORMITY. AN ADDITION SHALL NOT |
| | CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE ADDITION IS BEING MADE WITH |
| | REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE |
| | SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL, |
| | PLUMBING, OR ELECTRICAL SYSTEMS. |
| | |
| | 3B) UNDER THE HEADING OF PROJECT DATA THE PLANS |
| | INDICATE AN OCCUPANT LOAD OF 509 OCCUPANTS. PLEASE |
| | REVIEW SECTION 1102.3 OF THE EXIST. BUILD. CODE SECTION |
| | 1102.3 FIRE PROTECTION SYSTEMS. EXISTING FIRE AREAS |
| | INCREASED BY THE ADDITION SHALL COMPLY WITH CHAPTER 9 |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2017 FBC-B SECTION [F] 903.2.1.3 GROUP A-3. AN |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR FIRE |
| | AREAS CONTAINING GROUP A-3 OCCUPANCIES AND INTERVENING |
| | FLOORS OF THE BUILDING WHERE ONE OF THE FOLLOWING |
| | CONDITIONS EXISTS: 2.THE FIRE AREA HAS AN OCCUPANT LOAD |
| | OF 300 OR MORE. PLEASE PROVIDE FIRE SPRINKLERS AND |
| | PLANS FOR THIS BUILDING. |
| | |
| | 3C) UNDER THE HEADING OF PROJECT DATA THE PLANS |
| | INDICATE (2) REQUIRED EXITS. PLEASE REVIEW SECTION |
| | 1006.2.1.1 OF THE FBC-B 2017. 1006.2.1.1 THREE OR MORE |
| | EXITS OR EXIT ACCESS DOORWAYS. THREE EXITS OR EXIT |
| | ACCESS DOORWAYS SHALL BE PROVIDED FROM ANY SPACE WITH |
| | AN OCCUPANT LOAD OF 501 TO 1,000. PLEASE CORRECT PLANS. |
| | |
| | 4) THERE IS A NOTE ON SHEET A1 THAT THE FLOOR SLAB |
| | SLOPES DOWN +/- 10 INCHES FROM NORTH TO SOUTH. ON |
| | EITHER THE LIFE SAFETY SHEET OR THE A1 SHEET PLEASE |
| | PROVIDE WHERE THE FLOOR ELEVATION 100.00 WILL BE. THE 2 |
| | DETAILS SHEET A9 DETAIL A AND SHEET A10 DETAIL E BOTH |
| | SHOW THE FLOOR ELEVATION AT 100.00. DISCREPANCY IN |
| | PLANS? IS THE SLOPED FLOOR EXISTING AND BEING DONE AWAY |
| | WITH? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) SHEET S1 THE FOUNDATION PLAN PROVIDES THE FOUNDATION |
| | IS DESIGNED FOR 2,500 PSF AT 95% COMPACTION, BUT IN |
| | THIS SUBMITTAL THERE WAS NO SOILS REPORT SUBMITTED, |
| | THIS IS A QUESTIONABLE AREA WITH A CANAL SO CLOSE. 2017 |
| | FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 6) SHEET S1 HAS THE WIND DESIGN WITH BUILDING RISK |
| | CATEGORY III AND WIND SPEED (VULT) AS 180 MPH. THE |
| | PRESSURES GIVEN ARE FOR 50 SQ. FT. EFFECTIVE WIND AREA, |
| | BUT THE PLAN DOES NOT STATE IF THE PRESSURES ARE GIVEN |
| | IN VULT OR VASD? SHEET A5 ELEVATIONS PROVIDE PRESSURES |
| | FOR WALL ZONES 4 & 5 IN VULT , THE VULT PRESSURES ARE |
| | CORRECT. PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE |
| | PRODUCT APPROVALS ARE ALSO IN VASD. |
| | THANK YOU FOR YOUR CO-OPERATION IN THIS MATTER. |
| | |
| | 7) NEITHER SHEET S1 OR S2 PROVIDE THE PRESSURES +/- FOR |
| | ROOF ZONES 1, 2 OR 3 THE EFFECTIVE AREA SHOULD BE 10 |
| | SQ. FT. FOR THE ROOFING PRESSURES. 2017 FBC-B 1603.1.4 |
| | WIND DESIGN DATA. |
| | |
| | 8) THE SUBMITTED PRODUCT APPROVALS DOES NOT HAVE THE |
| | SHOP DRAWING STAMP OF APPROVALS FROM THE DESIGNER OF |
| | RECORD. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 9) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 10) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 11A) PLEASE NOTE THERE WAS A MIAMI-DADE NOA 17-1017.16 |
| | 3000 REGISTER ALUMINUM STOREFRONT WINDOW WALL SYSTEM |
| | SUBMITTED. THIS REPORT EXPIRED ON MARCH 18, 2019. |
| | REPORT NEEDS UPDATING. |
| | |
| | 11B THE REGISTER ALUMINUM STOREFRONT WINDOW WALL SYSTEM |
| | SUBMITTED IS ONLY FOR A WINDOW WALL SYSTEM, IT DOES NOT |
| | INCLUDE STOREFRONT DOOR SYSTEMS, MULLIONS AND SIDE |
| | LIGHTS, AND A SEPARATE REPORT IS REQUIRED. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 12) PLEASE NOTE SHEET A1 AT THE SANCTUARY PLATFORM |
| | INDICATES A NON-COMPLIANT ADA RAMP. THE OCCUPANT LOAD |
| | FOR THE SANCTUARY PLATFORM IS 96 OCCUPANTS REQUIRING 2 |
| | MEANS OF EGRESS FROM THE PLATFORM. PLEASE SEE IN THE |
| | 2017 FBC-BUILDING SECTION 1012.2 SLOPE. RAMPS USED AS A |
| | MEANS OF EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER |
| | THAN ONE UNIT VERTICAL IN 12 UNITS HORIZONTAL (8 % |
| | SLOPE). |
| | |
| | 13) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| | BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| | APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| | THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| | WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| | PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| | THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |