| 2019-08-12 15:06:47 | BUILDING PLAN REVIEW - NFIP |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I |
| | HAVE INCLUDED THEM BELOW FOR YOUR REVIEW. |
| | |
| | BUILDING PLAN REVIEW - NFIP |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NFIP REVIEW |
| | CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16 |
| | |
| | 1. BASED ON THE SUBMITTED SURVEY, THIS LOT AND PROPOSED |
| | IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE WITH A |
| | BASE FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD. |
| | 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY |
| | MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD |
| | INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY |
| | COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY |
| | OF WEST PALM BEACH, FL. |
| | 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED |
| | ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST |
| | PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT |
| | FREEBOARD ABOVE THE (BFE). |
| | 4. YOU MAY SUBMIT A SURVEY SHOWING ALL EXISTING AND |
| | PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET |
| | OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A |
| | STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD |
| | ELEVATION (DFE) WILL BE 9.4 FEET NAVD88 BASED ON THE |
| | (BFE) OF 7.00 FEET FOR FLOOD ZONE AE PLUS A CORRECTION |
| | FACTOR OF .4 FEET PLUS TWO FEET OF FREEBOARD. |
| | |
| | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| | REQUIRED AT TIME OF PERMIT APPLICATION. |
| | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS |
| | SITE ARE REQUIRED TO BE AT OR ABOVE 9 FEET 4 INCHES |
| | NAVD. |
| | |
| | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED |
| | FLOOR ELEVATION IS REQUIRED. |
| | |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING |
| | FINAL. |
| | |
| | GARAGE - VENTS |
| | |
| | G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. |
| | FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION |
| | SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO |
| | THE FOLLOWING: |
| | |
| | 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY |
| | WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS |
| | TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF |
| | FLOODWATERS. |
| | |
| | |
| | |