| 2019-08-12 14:59:29 | ELECTRICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | ITEMS 2 & 3 FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I | | | HAVE INCLUDED THEM MBELOW FOR YOUR REVIEW. | | | | | | | | | 2. LIGHTING IN CLOSETS IS SHOWN AS A 3 INCH LED | | | FIXTURE. PER CODE, LIGHTING WITH OPEN OR PARTIALLY | | | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS | | | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE | | | CLARIFICATION AND/OR CORRECTION. NEC 410.16; FBC RE | | | E4003.12 | | | 3. HIS AND HER CLOSET SHOW A CHANDELIER FIXTURE IN THE | | | CLOSET. PER CODE, LIGHTING WITH OPEN OR PARTIALLY | | | ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS | | | SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE | | | CORRECTION. NEC 410.16; FBC RE E4003.12 | | | | | | |
|