| 2019-08-12 14:53:41 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I |
| | HAVE INCLUDED THEM BELOW FOR YOUR REBIEW. |
| | |
| | |
| | ADDRESS: 5009 S FLAGLER PERMIT # 19050988 |
| | TYPE: BLD-RES NEW SFR |
| | |
| | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1. PROVIDE SOILS REPORT REVIEWED AND APPROVED BY |
| | DESIGNER OF RECORD. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SEPERATE GAS PERMIT IS REQUIRED. |
| | PERMITS |
| | 105.1 REQUIRED. |
| | |
| | 3. DESIGNER TO SELECT ICYNENE PRODUCT FROM PAGE 7 OF 8 |
| | OF THE PRODUCT APPROVAL TO BE INSTALLED. INSTALLATION |
| | INSTRUCTIONS SHALL BE ON-SITE AT TIME OF APPLICATION. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE INSULATION SUBMITTALS. |
| | |
| | 4. PRODUCT APPROVALS AND NOA'S SUBMITTED FOR REVIEW DO |
| | NOT MATCH THOSE ITEMS LISTED ON THE NOA COVER PAGE. |
| | THERE ARE MULTIPLE COPIES OF THE NOA COVER PAGE |
| | INCLUDED IN SUBMITTAL. REMOVE THOSE THAT DO NOT APPLY |
| | TO THIS PROJECT. |
| | ALL PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY DESIGNER. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | NEW COMMENT: |
| | |
| | 1. DESIGNER SHALL REVIEW AND APPROVE ALL PRODUCT |
| | APPROVALS. PLEASE INDICATE WHICH MODEL OR SYSTEM SHALL |
| | BE INSTALLED. |
| | |