| 2019-05-21 09:54:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | THE INSTALLATION SCHEDULE SUBMITTED HAS THE FOLLOWING | | | ISSUES, FBC R 301: | | | | | | 1. SEE SHEET 13 OF THE PRODUCT APPROVAL; AN EDGE | | | DISTANCE OF 3" REQUIRES A .78 FACTOR APPLIED TO THE | | | ANCHOR SPACING SPECIFIED IN THE CHARTS. | | | | | | 2. THE SHUTTER SPAN FOR ACCORDIONS SHOULD BE THE BLADE | | | LENGTH. SEE OPENING 1, 108 X 64; 115" IS SPECIFIED AS | | | SHUTTER SPAN. OPENING 3, 27X64 SPECIFIES 34". PLEASE | | | REVISE. | | | | | | 3. CONNECTION TYPE SPECIFIED IS W, BUT THAT IS FOR WOOD | | | SUBSTRATE AND MOUNTING TYPES A, D, AND I ARE CIRCLED ON | | | SHEETS 12, 14. | | | | | | |
|