Plan Review Notes
Plan Review Notes For Permit 19050931
Permit Number 19050931
Review Stop P
Sequence Number 1
Notes
Date Text
2019-06-21 17:07:221ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR.
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL. THE
 REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 3. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PLACE NOTE ON PLAN. PER FBC ACC 609.4
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  