| 2019-07-01 10:32:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-2.1: PLEASE CLARIFY NOTE #7 AND SHOW THE |
| | ROOF TOP LOCATIONS OF THE O/A INLETS FOR AHU'S 1, 2, & |
| | 3- SECTION 107.2.1 WPB. PLEASE INLCUDE CLEARANCE |
| | DISTANCE MEASUREMENTS PER SECTUION 401.4 FBC M. |
| | |
| | 2) SUBMIT NOA #17-1218.02. |
| | |
| | 3) ELECTRONIC PLANS: THE DIGITALLY SIGNED PLANS SHALL |
| | ALSO BEAR THIS STATEMENT IN ACCORDANCE WITH SECTION |
| | 61G15-23.005- "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED |
| | AND SEALED BY _________ON DATE________USING A SHA-1 |
| | AUTHENTICATION CODE." THE CURRENT MECHANICAL PLANS |
| | INDICATE THEY ARE SIGNED ONLY. IN ADDITION ENGINEERS |
| | MAY NOT SELF-CERTIFY ELECTRONIC SIGNATURES AND SEALS. |
| | CERTIFICATION SHALL BE BY A THIRD-PARTY AGENCY. |
| | |
| | 4) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AND |
| | RELOCATED AIR HANDLERS- SECTION 307.2.1 GFBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |