Plan Review Notes
Plan Review Notes For Permit 19050931
Permit Number 19050931
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-06-04 11:19:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G001 - THERE ARE INCORRECT EDITIONS INDICATION
 UNDER THE FLORIDA FIRE PREVENTION CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET G 001 - THE ADDRESS INDICATED ON THE
 APPLICATION IS 2442 METROCENTRE BLVD E; HOWEVER, THE
 TITLE BLOCK INDICATION 2474.
  
 PLEASE REVIEW, CORRECT TO THE PROPER ADDRESS OR JUSTIFY
 WITH DETAILS.
  
  
  
 3) SHEET G 001 & A 101 - THERE ARE INDICATIONS OF FIRE
 ALARM CONSULTANTS AND FIRE ALARM EQUIPMENT (WITHIN THE
 SYMBOL LEGEND).
  
 PLEASE CLARIFY IF A FIRE ALARM IS EXISTING, PROPOSED OR
 NONAPPLICABLE.
  
  
  
 4) SHEET G 001 - THERE IS AN INDICATION OF A FIRE
 PROTECTION CONSULTANT, BUT NO INDICATION OF FIRE
 PROTECTION EQUIPMENT.
  
 PLEASE CLARIFY IF A FIRE SPRINKLER PROTECTION IS
 EXISTING, PROPOSED OR NONAPPLICABLE.
  
  
  
 5) SHEET A 101 - THERE ARE INDICATIONS OF CARD READER
 AT SOME LOCATIONS.
  
 CARD READER SHALL BE SUBMITTED UNDER SEPRATE PERMIT AND
 SHOP DRAWINGS.
  
 CARD READER WITHIN A MEANS OF EGRESS SHALL COMPLY WITH
 NFPA 101, CH 7.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN AN
 APPLICABLE NOTE
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  