| 2019-06-04 11:19:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET G001 - THERE ARE INCORRECT EDITIONS INDICATION |
| | UNDER THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| | |
| | PLEASE REVIEW, CORRECT AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | 2) SHEET G 001 - THE ADDRESS INDICATED ON THE |
| | APPLICATION IS 2442 METROCENTRE BLVD E; HOWEVER, THE |
| | TITLE BLOCK INDICATION 2474. |
| | |
| | PLEASE REVIEW, CORRECT TO THE PROPER ADDRESS OR JUSTIFY |
| | WITH DETAILS. |
| | |
| | |
| | |
| | 3) SHEET G 001 & A 101 - THERE ARE INDICATIONS OF FIRE |
| | ALARM CONSULTANTS AND FIRE ALARM EQUIPMENT (WITHIN THE |
| | SYMBOL LEGEND). |
| | |
| | PLEASE CLARIFY IF A FIRE ALARM IS EXISTING, PROPOSED OR |
| | NONAPPLICABLE. |
| | |
| | |
| | |
| | 4) SHEET G 001 - THERE IS AN INDICATION OF A FIRE |
| | PROTECTION CONSULTANT, BUT NO INDICATION OF FIRE |
| | PROTECTION EQUIPMENT. |
| | |
| | PLEASE CLARIFY IF A FIRE SPRINKLER PROTECTION IS |
| | EXISTING, PROPOSED OR NONAPPLICABLE. |
| | |
| | |
| | |
| | 5) SHEET A 101 - THERE ARE INDICATIONS OF CARD READER |
| | AT SOME LOCATIONS. |
| | |
| | CARD READER SHALL BE SUBMITTED UNDER SEPRATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | CARD READER WITHIN A MEANS OF EGRESS SHALL COMPLY WITH |
| | NFPA 101, CH 7. |
| | |
| | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| | ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN AN |
| | APPLICABLE NOTE |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |