2019-06-17 15:44:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RECEPTACLE OUTLETS WITHIN 6 FEET OF A SINK REQUIRE
 GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 2. PROVIDE DEMAND LOAD FOR EACH PHASE OF PANEL C1. THE
 CURRENT LOAD STATED FOR A PHASE SHOWS A LOAD OF 214
 AMPS ON A 200 AMP PANEL. PROVIDE CORRECTION. NEC
 408.30, 408.36, 215.2, 310.15
  
 END OF COMMENTS.
  