2019-07-15 08:49:592017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050931
 ADD: 2478 METROCENTRE BLVD. E
 CONT: BLUEFIN CONSTRUCTION, INC.
 TEL: 954-428-1011
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 15/ 2019
 ACTION: DENIED
  
 1) THE COVERSHEET G001:
  
 1A) PLEASE UPDATE CODE REFERENCE MAXIMUM COMMON PATH OF
 TRAVEL THE PLANS REFERENCE TABLE 1014.3. IN THE 2017
 FBC-B COMMON PATH OF TRAVEL IS FOUND IN SECTION 106.2.1
 AND TABLE 1006.2.1.
  
 1B) PLEASE UPDATE THE CODE REFERENCE FOR THE MAXIMUM
 TRAVEL DISTANCE. THE COVERSHEET REFERENCES TABLE
 1016.2. IN THE 2017 FBC-B THE MAXIMUM TRAVEL DISTANCES
 ARE FOUND IN TABLE 1017.2 OF THE 2017 FBC-B. PLEASE
 UPDATE THE CODE REFERENCES.
  
 1C) PLEASE UPDATE THE CODE REFERENCES FOR MINIMUM
 CORRIDOR WIDTH, THE PLANS STATE SECTION 1018.2. IN THE
 2017 FBC-B SECTION 1020.2 & TABLE 1020.2 WOULD BE THE
 SECTIONS TO REFERENCE.
  
 1D) THE COVERSHEET ALSO LIST DEAD ENDS FOUND IN SECTION
 1018.4. IN THE 2017 FBC-B DEAD ENDS ARE FOUND 1020.4.
 PLEASE UPDATE PLANS TO THE 2017 FBC-B.
  
 1E) PLEASE ALSO UPDATE THE CODE REFERENCE FOR THE NO.
 OF EXITS, SECTION 1021. IN THE 2017 FBC-B THE NUMBER OF
 REQUIRED EXITS OR EXIT ACCESS DOORWAYS IS FOUND UNDER
 SECTION & TABLE 1006.2.1.
  
 1F) THE NUMBER OF REQUIRED EXITS OR EXIT ACCESS TO
 EXITS PER STORY IS FOUND IN SECTION & TABLE 1006.3.1.
  
 1G) IT IS ASSUMED THAT THIS IS A NON-SPRINKLERED
 BUILDING WITH THE VARIOUS DISTANCES GIVEN IN THE ABOVE
 TABLES. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET 004-A121 THE FLOOR PLAN INDICATES THE CORRIDOR
 BUT THE LENGTH IS NOT GIVEN. WHEN THE PLANS ARE
 CALIBRATED FOR MEASUREMENTS THE LENGTH OF THE DEAD END
 CORRIDOR IS APPROXIMATELY 28 FEET. IT IS ASSUMED THIS
 IS A NON-SPRINKLERED BUILDING LIMITING THE LENGTH OF A
 DEAD END CORRIDOR TO 20 FEET. THE LIFE SAFETY SHEET
 DOES NOT INDICATE WITH AN EXIT DIRECTIONAL GOING
 THROUGH THE STORAGE ROOM AND THIS IS CORRECT SINCE
 SECTION 1016.2 EGRESS THROUGH INTERVENING SPACES DOES
 NOT ALLOW EGRESS THROUGH STORAGE ROOMS. THE EXIT SIGN
 WITHIN THE STORAGE ROOM IS CORRECT SINCE IT IS ONLY FOR
 THIS ROOM.
  
 3) PLEASE PROVIDE AN EXPLANATION OF WHERE THE INTERIOR
 AND EXTERIOR OF THE BUILDING IS IN RELATION TO THE
 NORTH WALL WITH WINDOWS, DOORS AND OVERHEAD EXTERIOR
 DOOR. BOTH THIS AREA AND THE OPPOSITE SIDE OF THE
 TENANT SEPARATION WALL ARE BOTH SHADED WITH THE SAME
 GRAY. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A405 ADA STANDARDS NEED TO UPDATE THE HEIGHT
 OF GRAB BARS TO THE 2017 FBC-ACCESSIBILITY CODE SECTION
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 5) SHEET A410 DETAILS THE INTERIOR ELEVATIONS & DETAIL
 D CABINET BASE @ MICROWAVE SHELF. IN BOTH DETAILS THEY
 SHOW THE BOTTOM OF THE SHELF THAT HOLDS THE MICROWAVE
 ARE LOCATED 4 FEET 10 INCHES ABOVE THE FINISH FLOOR.
 PLEASE CORRECT THE PLANS TO SHOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE SECTIONS:
  
 5A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 5B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 6) THE MECHANICAL PLANS M-2.1 NOTE 14 INDICATE THE
 INSTALLATION OF A A/C STAND ON THE ROOF. PLEASE PROVIDE
 COMPLIANCE WITH:
 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 6A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) THE ROOF TOP A/C STAND PRODUCT APPROVAL A
 MIAMI-DADE NOA # 17-1218.02 WAS INDICATED ON SHEET
 M2.1. THIS NOA NEEDS TO BE REVIEWED BY THE DESIGNER OF
 RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 7) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  