Plan Review Notes
Plan Review Notes For Permit 19050890
Permit Number 19050890
Review Stop R
Sequence Number 2
Notes
Date Text
2019-09-13 16:46:221- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR ROOFING AT NEW COVERED TERRACE.
 NOTE: COORDINATE WITH ITEM #4(B) ABOVE.
  
 ORIGINAL COMMENT:
 A)IF FLAT ROOF, THEN PROVIDE THE FOLLOWING:
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AS
 REQUIRED BY FAC 61G20-3.001 AND CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.2.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 THIS MAY BE SUBMITTED LATER AS A DEFERRED SUBMITTAL.
 BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 B)IF TILE ROOF, THEN PROVIDE THE FOLLOWING:
 - ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL. IF SPECIFYING SCREWS, THEN
 SPECIFY SCREW SIZE AND NUMBER OF SCREWS.
 -ROOF TILE PRODUCT APPROVAL AND CLEARLY MARK ROOF TILE
 FASTENING METHOD AS REQUIRED BY CITY POLICY FOR ALL
 ROOFING PERMITS.
  
 RESPONSE:
 ENGINEER NEEDS TO PROVIDE THE ROOF TILE FASTENING
 METHOD. IF USING SCREWS, THEN NEED TO SPECIFY SIZE AND
 NUMBER OF SCREWS.
  
 ORIGINAL COMMENT:
 2- OWNER/BUILDER NEEDS TO COMPLETE ROOFING PERMIT
 APPLICATION ALSO. SEC/ 105.1 CITY AMENDMENTS.
  
 RESPONSE:
 NEED THE ROOFING PRODUCT APPROVALS BEFORE ISSUING THE
 ROOFING SUB-PERMIT. ROOFING PERMIT APPLICATION WILL BE
 ON HOLD UNTIL PRODUCT APPROVALS ARE SUBMITTED.
  