Plan Review Notes
Plan Review Notes For Permit 19050890
Permit Number 19050890
Review Stop B
Sequence Number 2
Notes
Date Text
2019-09-12 17:18:49RESIDENTIAL (R3) SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
  
 -ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 1- OK
  
 2- REVISE INFORMATION ON SHEET A-1:
  
 ORIGINAL COMMENT:
 A)ACCORDING TO CITY RECORDS AND PALM BEACH COUNTY
 PROPERTY APPRAISER THESE BUILDINGS WERE BUILT IN 1925
 AND THEIR CONSTRUCTION WAS WOOD FRAME. DESIGN CRITERIA
 STATES CONSTRUCTION TYPE IIIB. THIS IS INCORRECT.
 REVISE AS REQUIRED. SEC. 602.1 FBC-BUILDING.
  
 RESPONSE:
 REVISED CONSTRUCTION TYPE IS INCORRECT AGAIN. WOOD
 FRAMED BUILDINGS ARE NOT TYPE IIB CONSTRUCTION.
 ENGINEER TO SEE SEC. 602.2 FBCBUILDING FOR CONSTRUCTION
 TYPE II REQUIREMENTS. FBC-BUILDING. THIS BUILDING FALLS
 MORE INTO THE TYPE VB CONSTRUCTION. REVISE AS REQUIRED.
  
 B)OK.
  
 C) OK
  
 3- GUEST HOUSE PROPOSED FLOOR PLAN ON SHEET A-2:
 A)OK
  
 ORIGINAL COMMENT:
 B) THIS IS A WOOD FRAMED BUILDING NOT CONCRETE BLOCK.
 SEE ITEM #2(A) ABOVE. REVISE DETAILS AND SPECIFICATIONS
 SHOWN ON THE FLOOR PLAN, PARTITION ASSEMBLY LEGEND AND
 RESPECTIVE LEGEND AND KEY NOTES ON SHEET A-2. AND,
 PROVIDE WOOD FRAMING REINFORCEMENT
 DETAILS/SPECIFICATIONS AT EXTERIOR DOORS OPENINGS IF
 REQUIRED. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 (1) THE LEGEND FOR THE PARTITION ASSEMBLY LEGEND IS NOT
 CLEAR. WHAT IS AN 8" WOOD WALL MASONRY UNIT SPECIFIED
 ON LEGEND NOTE #1?. IT LOOKS LIKE THE ENGINEER IS
 MISMATCHING WOOD FRAMED CONSTRUCTION AND MASONRY
 CONSTRUCTION. CLARIFY./REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 (2) THE MINIMUM STUCCO THICKNESS IS 7/8" NOT 3/4". SEE
 TABLE R702.1(1) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 (3) PROVIDE DETAIL SHOWING HOW INSTALLING THE 1"X2"
 PRESSURE TREATED FURRING STRIPS SPECIFIED ON LEGEND
 NOTE #3. THIS TYPE CONSTRUCTION IS USUALLY SPECIFIED ON
 MASONRY CONSTRUCTION. IF ENGINEER WANTS TO USE THIS
 FURRING STRIPS, THEN PROVIDE THE REQUESTED DETAIL. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 (4)PROVIDE DETAIL SHOWING HOW INSTALLING THE FOIL
 INSULATION R-4 ON THE FRAMED WALL AS SPECIFIED ON
 LEGEND NOTE #4. THIS TYPE OF INSULATION IS USUALLY
 SPECIFIED ON MASONRY CONSTRUCTION. IF ENGINEER WANTS TO
 USE THIS INSULATION , THEN PROVIDE THE REQUESTED
 DETAIL. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 (5) WALL TYPE #1 SHOWS 1/2" GYPSUM BOARD ON BOTH SIDES
 OF WALL. THIS IS AN EXTERIOR WALL. THIS SEEMS TO BE
 INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 (6) FIRE RATED WALL #3 IS INCORRECT. WALL TYPE #3 SHOWN
 DOESN'T CORRESPOND TO UL-425. UL 425 ASSEMBLY IS FOR
 WALL WITH METAL STUDS NOT WOOD FRAME. REVISE AS
 REQUIRED. PROVIDE ASSEMBLY DETAILS THAT MATCHES
 APPROVED ASSEMBLY. SEC. 107.2.1.2 CITY AMENDMENTS.
  
  
 C) OK
  
 D)OK
  
 ORIGINAL COMMENT:
 E) BASED ON THE LOCATION OF THE EXISTING STRUCTURE THE
 SOUTH WALL NEEDS TO BE ONE HOUR FIRE RATED WALL AS
 REQUIRED BY TABLE R302.1 FBC-RESIDENTIAL. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR ONE HOUR FIRE
 RATED WALL.
  
 RESPONSE:
 REVISE PARTITION ASSEMBLY #3. ONE HOUR FIRE RATED UL
 ASSEMBLY 425 SPECIFIED ON SHEET A-2 IS FOR METAL STUDS
 PARTITION. REVISE AS REQUIRED. COORDINATE WITH ITEM
 #B(6) ABOVE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
  
 F) OK.
  
 G)OK
  
 4- SHEET S-1:
 A) OK.
  
 ORIGINAL COMMENT:
 B)NEW COVERED TERRACE ROOFING MATERIAL IS NOT CLEAR.
 SECTION A ON SHEET S-1 SPECIFIES MODIFIED BITUMEN,
 WHILE EXTERIOR ELEVATIONS ON SHEET A-3 SHOW SOME KIND
 OF ROOF TILE. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
 NOTE: TO AVOID CONFLICTS/DELAYS KEEP IN MIND THAT THERE
 ARE LIMITATIONS ON THE MINIMUM ROOF SLOPE AS REQUIRED
 BY SEC. R905.3.2 FBC-RESIDENTIAL AND PRODUCT APPROVALS.
  
 RESPONSE:
 (1) SECTION "A" WAS REVISED. IT CALLS FOR CEMENT TILE.
 SLOPE OF DECK NEEDS TO COMPLY WITH SEC. 905.3.2
 FBC-RESIDENTIAL. SECTION A SPECIFIES 1" SLOPE. CLEARLY
 SPECIFY THE SLOPE OF THE DECK IN DEGREES, GRADIENT OR
 PERCENT. IT LOOKS LIKE THE CONCRETE TILE MAY NOT BE
 INSTALLED AS PROPOSED. SEE FRSA/TRI CONCRETE AND CLAY
 TILE INSTALLATION MANUAL AND CONCRETE TILE PRODUCT
 APPROVAL FOR MINIMUM SLOPE REQUIRED.
  
  
  
 5- ENERGY CALCULATIONS SUBMITTED:
 NOTE: THIS STRUCTURE IS A CONTRIBUTING HISTORIC HOUSE.
 UNFORTUNATELY THIS WAS NO PROPERLY FLAGGED IN THE CITY
 SYSTEM. THAT'S WHY THIS ISSUE WAS NOT ADDRESSED ON THE
 FIRST REVIEW. ENERGY CALCULATIONS ARE NOT REQUIRED FOR
 CONTRIBUTING HISTORIC BUILDINGS. BUT IF OWNER WANTS TO
 SUBMIT THEM, THEN THEY NEED TO BE COMPLETE AND CORRECT.
  
 ORIGINAL COMMENT:
 A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM BY THE OWNER OR THE OWNER LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 RESPONSE:
 ONLY ONE COPY WAS SIGNED. NEED TO SIGN BOTH COPIES.
  
 ORIGINAL COMMENT:
 B) CALCULATIONS HAVE A COPY OF A DIGITAL SIGNATURE.
 THIS IS NOT A DIGITAL SUBMITTAL. CALCULATIONS NEED TO
 HAVE THE ORIGINAL SEAL AND SIGNATURE AND INFORMATION OF
 THE ENGINEER OF RECORD AS REQUIRED BY SEC. 61G15-23.003
 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 RESPONSE:
 ENGINEER DIDN'T PROVIDE HIS INFORMATION AS REQUIRED BY
 CHAPTER 471 F.S.
  
 ORIGINAL COMMENT:
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING THE OWNER'S NAME, BUILDER'S NAME,
 PERMIT OFFICE AND JURISDICTION SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 RESPONSE:
 STILL MISSING INFORMATION. NEED THE BUILDER'S NAME AND
 PERMIT OFFICE.
  
 D) OK
  
 E) OK
  
 F)OK
  
 G)OK
  
 ORIGINAL COMMENT:
 H)REVISE TYPE OF ROOF AND ROOF MATERIAL SPECIFIED ON
 PAGE 2 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 ROOF MATERIAL IS INCORRECT. SEE PLANS AND REVISE AS
 REQUIRED.
  
 I)OK
  
 J)OK
  
 ORIGINAL COMMENT:
 K)REVISE WINDOWS ORIENTATION SHOWN ON PAGE 3 OF 4. THE
 ORIENTATION OF THE WINDOWS DON'T MATCH PLANS (NOTE:
 PLANS ARE DRAWN WITH THE NORTH ARROW FACING DOWN. KEEP
 THIS IN MIND WHEN REVISING THE CALCULATIONS). SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 THERE ARE NO OPENINGS ON THE EAST SIDE. SEE PLANS AND
 REVISE AS REQUIRED.
  
 L) OK
  
 M)OK
  
 ORIGINAL COMMENT:
 N)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 BUILDER (OWNER/BUILDER) DIDN'T COMPLETE THE EPL DISPLAY
 CARD.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- OK.
  
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR ROOFING AT NEW COVERED TERRACE.
 NOTE: COORDINATE WITH ITEM #4(B) ABOVE.
  
 ORIGINAL COMMENT:
 A)IF FLAT ROOF, THEN PROVIDE THE FOLLOWING:
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AS
 REQUIRED BY FAC 61G20-3.001 AND CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.2.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 THIS MAY BE SUBMITTED LATER AS A DEFERRED SUBMITTAL.
 BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 B)IF TILE ROOF, THEN PROVIDE THE FOLLOWING:
 - ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL. IF SPECIFYING SCREWS, THEN
 SPECIFY SCREW SIZE AND NUMBER OF SCREWS.
 -ROOF TILE PRODUCT APPROVAL AND CLEARLY MARK ROOF TILE
 FASTENING METHOD AS REQUIRED BY CITY POLICY FOR ALL
 ROOFING PERMITS.
  
 RESPONSE:
 ENGINEER NEEDS TO PROVIDE THE ROOF TILE FASTENING
 METHOD. IF USING SCREWS, THEN NEED TO SPECIFY SIZE AND
 NUMBER OF SCREWS.
  
 8- OK.
  
 ORIGINAL COMMENT:
 9- OWNER/BUILDER NEEDS TO COMPLETE ROOFING PERMIT
 APPLICATION ALSO. SEC/ 105.1 CITY AMENDMENTS.
  
 RESPONSE:
 NEED THE ROOFING PRODUCT APPROVALS BEFORE ISSUING THE
 ROOFING SUB-PERMIT. ROOFING PERMIT APPLICATION WILL BE
 ON HOLD UNTIL PRODUCT APPROVALS ARE SUBMITTED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 TO AVOID MULTIPLE SUBMITTALS PLEASE CONTACT ME IF YOU
 HAVE ANY QUESTIONS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  