Plan Review Notes
Plan Review Notes For Permit 19050890
Permit Number 19050890
Review Stop R
Sequence Number 1
Notes
Date Text
2019-06-17 15:58:061- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR ROOFING AT NEW COVERED TERRACE.
 NOTE: COORDINATE WITH ITEM #4(B) ABOVE.
  
 A)IF FLAT ROOF, THEN PROVIDE THE FOLLOWING:
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AS
 REQUIRED BY FAC 61G20-3.001 AND CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.2.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)IF TILE ROOF, THEN PROVIDE THE FOLLOWING:
 - ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL. IF SPECIFYING SCREWS, THEN
 SPECIFY SCREW SIZE AND NUMBER OF SCREWS.
 -ROOF TILE PRODUCT APPROVAL AND CLEARLY MARK ROOF TILE
 FASTENING METHOD AS REQUIRED BY CITY POLICY FOR ALL
 ROOFING PERMITS.