Plan Review Notes
Plan Review Notes For Permit 19050890
Permit Number 19050890
Review Stop B
Sequence Number 1
Notes
Date Text
2019-06-14 19:04:26RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 1-PLANS SUBMITTED HAVE A COPY OF A DIGITAL SIGNATURE.
 THIS IS NOT A DIGITAL SUBMITTAL. ALL PLANS NEED TO HAVE
 THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF
 RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER
 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS
  
 2- REVISE INFORMATION ON SHEET A-1:
 A)ACCORDING TO CITY RECORDS AND PALM BEACH COUNTY
 PROPERTY APPRAISER THESE BUILDINGS WERE BUILT IN 1925
 AND THEIR CONSTRUCTION WAS WOOD FRAME. DESIGN CRITERIA
 STATES CONSTRUCTION TYPE IIIB. THIS IS INCORRECT.
 REVISE AS REQUIRED. SEC. 602.1 FBC-BUILDING.
  
 B) THIS IS NOT AN ALTERATION LEVEL 2. THE CONVERSION OF
 THE EXISTING GARAGE TO LIVABLE SPACE IS A CHANGE OF USE
 AND ALTERATION LEVEL 3. REVISE AS REQUIRED. SEC. 505
 AND SEC. 506 FBC-EXISTING BUILDING. REVISE AS REQUIRED.
  
 C) SITE PLAN STATES THAT THE REAR STRUCTURE IS
 "EXISTING GUEST HOUSE". THIS IS INCORRECT. THIS AN
 EXISTING GARAGE NOT EXISTING GUEST HOUSE. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- GUEST HOUSE PROPOSED FLOOR PLAN ON SHEET A-2:
 A)TYPICALLY ZONING DOESN'T ALLOW SEPARATE COOKING
 FACILITIES ON SINGLE FAMILY RESIDENCES. COORDINATE WITH
 ZONING REVIEW COMMENTS. IF ZONING DOESN'T ALLOW THE
 KITCHENETTE, THEN NEED TO REVISE PLANS ACCORDINGLY,
 INCLUDING CHANGING THE NAME OF THE AREA SO IT DOESN'T
 IMPLY THAT ANY KIND OF COOKING IS APPROVED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) THIS IS A WOOD FRAMED BUILDING NOT CONCRETE BLOCK.
 SEE ITEM #2(A) ABOVE. REVISE DETAILS AND SPECIFICATIONS
 SHOWN ON THE FLOOR PLAN, PARTITION ASSEMBLY LEGEND AND
 RESPECTIVE LEGEND AND KEY NOTES ON SHEET A-2. AND,
 PROVIDE WOOD FRAMING REINFORCEMENT
 DETAILS/SPECIFICATIONS AT EXTERIOR DOORS OPENINGS. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 C) THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE
 SPACE. THEREFORE, THE RISK CATEGORY IS HIGHER. ENGINEER
 OF RECORD TO PROVIDE ANALYSIS THAT THE EXISTING
 STRUCTURE COMPLIES WITH THE APPLICABLE WIND LOADS AS
 REQUIRED BY SEC. 1007.2 FBC-EXISTING BUILDING.
  
 D)BASED ON THE LOCATION OF THE EXISTING STRUCTURE
 OPENINGS IN THE REAR WALL (SOUTH WALL) ARE NOT ALLOWED.
 REVISE AS REQUIRED . SEC. R302.1 AND TABLE R302.1
 FBC-RESIDENTIAL. PROVIDE DETAILS AND SPECIFICATIONS FOR
 INFILL OF EXISTING OPENINGS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 E) BASED ON THE LOCATION OF THE EXISTING STRUCTURE THE
 SOUTH WALL NEEDS TO BE ONE HOUR FIRE RATED WALL AS
 REQUIRED BY TABLE R302.1 FBC-RESIDENTIAL. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR ONE HOUR FIRE
 RATED WALL.
  
 F) THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE
 SPACE. TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR
 VAPOR BARRIER. ENGINEER OF RECORD TO PROVIDE
 SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS
 REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL.
  
 G)PROVIDE DETAILS AND SPECIFICATIONS FOR THE INSULATION
 ON WALLS AND CEILINGS AS REQUIRED BY SEC. R103.2
 FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH THE
 ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS.
  
 4- SHEET S-1:
 A) EXISTING BUILDINGS ARE WOOD FRAMED BUILDINGS NOT
 CONCRETE BLOCK. REVISE ALL PLANS AND DETAILS THAT ARE
 REFERENCING CONCRETE BLOCK CONSTRUCTION. SEC. 107.2.1
 CITY AMENDMENTS. COORDINATE WITH ITEM #3(B) ABOVE.
  
 B)NEW COVERED TERRACE ROOFING MATERIAL IS NOT CLEAR.
 SECTION A ON SHEET S-1 SPECIFIES MODIFIED BITUMEN,
 WHILE EXTERIOR ELEVATIONS ON SHEET A-3 SHOW SOME KIND
 OF ROOF TILE. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
 NOTE: TO AVOID CONFLICTS/DELAYS KEEP IN MIND THAT THERE
 ARE LIMITATIONS ON THE MINIMUM ROOF SLOPE AS REQUIRED
 BY SEC. R905.3.2 FBC-RESIDENTIAL AND PRODUCT APPROVALS.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM BY THE OWNER OR THE OWNER LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 B) CALCULATIONS HAVE A COPY OF A DIGITAL SIGNATURE.
 THIS IS NOT A DIGITAL SUBMITTAL. CALCULATIONS NEED TO
 HAVE THE ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF
 RECORD AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER
 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING THE OWNER'S NAME, BUILDER'S NAME,
 PERMIT OFFICE AND JURISDICTION SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
 NOTE: DESIGN LOCATION AND JURISDICTION NUMBER ARE
 INCORRECT. PROVIDE CORRECT INFORMATION.
  
 D) MISSING ALL THE WINDOWS INFORMATION ON ITEM #7 OF
 PAGE 1 OF 4. NEED TO SPECIFY ALL GLASS AREA OF ENTRY
 DOOR AND AND SLIDING GLASS DOORS AS REQUIRED BY SEC.
 R405.5.3.1 AND SEC. R405.5.33 FBC-ENERGY CONSERVATION.
  
 E) REVISE ITEM #10 ON PAGE 1 OF 4. PLANS DON'T SPECIFY
 ANY UNDER ATTIC VENTING. REVISE AS REQUIRED TO MATCH
 PLANS OR PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE VENTING REQUIREMENTS. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)DESIGN LOCATION SHOWN ON PAGE 2 OF 4 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY
  
 G)PAGE 2 OF 4 INDICATES THAT THERE IS A KITCHEN IN THE
 GUEST HOUSE. THIS NEEDS TO BE COORDINATED WITH ITEM
 #3(A) ABOVE. IF ZONING DOESN'T ALLOW THE KITCHENETTE,
 THEN ENERGY CALCULATIONS WOULD NEED TO BE REVISED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE TYPE OF ROOF AND ROOF MATERIAL SPECIFIED ON
 PAGE 2 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5.
 TYPICALLY, THE RATIO IS 1/150 NOT 1/300. SEC. R806.2
 FBC-RESIDENTIAL. OR, PERSON PREPARING THE ENERGY
 CALCULATIONS TO PROVIDE COMPLETE DOCUMENTATION SHOWING
 COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY THE
 EXCEPTION ON SEC. R806.2.
 NOTE: COORDINATE WITH ITEM #5(E) ABOVE.
  
 J)REVISE DOOR INFORMATION PAGE 3 OF 4. THERE ARE NOT
 DOORS ON THE EAST SIDE. AND, THERE ARE NO WOOD DOORS
 EITHER. SEE PLANS AND PRODUCT APPROVALS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION.
  
 K)REVISE WINDOWS ORIENTATION SHOWN ON PAGE 3 OF 4. THE
 ORIENTATION OF THE WINDOWS DON'T MATCH PLANS (NOTE:
 PLANS ARE DRAWN WITH THE NORTH ARROW FACING DOWN. KEEP
 THIS IN MIND WHEN REVISING THE CALCULATIONS). SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 L) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE
 3 OF 4 TO MATCH PLANS. SEE PLANS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)REVISE WINDOWS INFORMATION ON PAGE 3 OF 4 TO MATCH
 PLANS. COORDINATE WITH ITEM #3(D) ABOVE AND WITH
 GLAZING IN DOORS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 N)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- WIND LOAD CALCULATIONS SUBMITTED HAVE A COPY OF A
 DIGITAL SIGNATURE. THIS IS NOT A DIGITAL SUBMITTAL.
 CALCULATIONS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR ROOFING AT NEW COVERED TERRACE.
 NOTE: COORDINATE WITH ITEM #4(B) ABOVE.
  
 A)IF FLAT ROOF, THEN PROVIDE THE FOLLOWING:
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AS
 REQUIRED BY FAC 61G20-3.001 AND CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.2.1
 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)IF TILE ROOF, THEN PROVIDE THE FOLLOWING:
 - ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL. IF SPECIFYING SCREWS, THEN
 SPECIFY SCREW SIZE AND NUMBER OF SCREWS.
 -ROOF TILE PRODUCT APPROVAL AND CLEARLY MARK ROOF TILE
 FASTENING METHOD AS REQUIRED BY CITY POLICY FOR ALL
 ROOFING PERMITS.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AND INCLUDE THE DESIGN
 PROFESSIONAL FEES.
  
  
 9- OWNER/BUILDER NEEDS TO COMPLETE ROOFING PERMIT
 APPLICATION ALSO. SEC/ 105.1 CITY AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  