Plan Review Notes For Permit 19050885
Permit Number 19050885
Review Stop R
Sequence Number 2
Notes
Date Text
2019-08-01 17:55:17ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL).
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT FLAT ROOF
 PRODUCT APPROVAL WILL BE SUBMITTED WITH SEPARATE
 ROOFING PERMIT.. THIS IS OK TO BE DONE WHEN GETTING THE
 ROOFING SUB-PERMIT.
  
 A)FLAT ROOF AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: FLAT ROOF PRODUCT APPROVAL NEEDS TO BE
 REVIEWED/APPROVED BY ARCHITECT OF RECORD PRIOR TO
 SUBMITTAL TO THIS OFFICE.