2019-06-07 19:14:05RESIDENTIAL(R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
 1- PROVIDE COMPLETE ENERGY CALCULATIONS (2 COPIES) AS
 REQUIRED BY SEC. 1106 FBC-EXISTING BUILDING AND SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH PLANS (SEE ENERGY CODE NOTES ON
 SHEET A-01) AND PRODUCT APPROVALS SUBMITTED TO AVOID
 CONFLICTS/DELAYS.
  
 2- SHEET A-01:
 A) REVISE THE WIND DESIGN DATA SHOWN UNDER THE CODE
 INFORMATION. THE CITY ULTIMATE DESIGN WIND SPEED IS 170
 MPH AND THE CORRESPONDING NOMINAL DESIGN WIND SPEED IS
 132 MPH. SEC. 120 CITY AMENDMENTS AND TABLE R301.2.1.3
 FBC-RESIDENTIAL.
  
 B)REVISE THE WIND ZONE INFORMATION SHOWN UNDER THE CODE
 INFORMATION. INFORMATION GIVEN "WIND ZONE 4: BASIC WIND
 SPEED > 160MPH" IS INCORRECT. SEE SEC. R301.2.1.2.1
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 C)REVISE THE CODE INFORMATION REFERENCED ON THE TOP
 RIGHT CORNER OF THE SHEET. THE CURRENT BUILDING CODE IS
 THE 6TH EDITION NOT THE 5TH EDITION. NOTE: THIS COMMENT
 APPLIES TO ALL SHEETS.
 CHAPTER 553 F.S.
  
 3- SHEET A-02:
 A)CLARIFY IF THE DESIGN PRESSURES SHOWN ON THE EXTERIOR
 ELEVATIONS FOR THE DOORS AND WINDOWS ARE THE ULTIMATE
 OR NOMINAL DESIGN PRESSURES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 B) PROVIDE ICC EVALUATION REPORT (OR ANY OTHER APPROVED
 EVALUATION REPORT) FOR THE CLOSED CELL SPRAY FOAM
 INSULATION SPECIFIED ON THE MIDDLE OF THE SHEET FOR THE
 UNVENTED ATTIC. TO SHOW COMPLIANCE WITH THE
 REQUIREMENTS OF SEC. R316 FBC-RESIDENTIAL.
 NOTE: COORDINATE R VALUE TO AVOID CONFLICTS/DELAYS.
 SPECIFICATIONS IN THIS SHEET CALL FOR R-40 SPRAY FOAM
 INSULATION, WHILE SPECIFICATIONS ON SHEET A-01 AND
 OTHER DETAILS ON SHEET S-01 CALL FOR R-30. COORDINATE
 TO MATCH.
  
 C) UPDATE THE PRODUCT APPROVALS NUMBERS SHOWN ON THE
 EXTERIOR DOOR & WINDOW SCHEDULE. THEY DON'T MATCH THE
 CURRENT PRODUCT APPROVALS SUBMITTED.
 FAC 61G20.3.001.
  
 4- SHEET S-01:
 A) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC.
 R703.1.2.1 FBC-RESIDENTIAL.
 ALSO, PROVIDE COMPLETE SPECIFICATIONS FOR THE FASCIA,
 INCLUDING ATTACHMENT. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) NEED TO SPECIFY RING SHANK NAILS ON ALL DETAILS ON
 THIS SHEET PROVIDING SPECIFICATIONS FOR THE ROOF
 SHEATHING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 C)DETAIL S-7: NEED TO REVISE CONNECTOR SPECIFIED FOR
 CONNECTION BETWEEN DOUBLE TOP PLATES AND ROOF JOIST.
 SIMPSON H16 IS A CONNECTOR TO BE USED IN MASONRY
 CONSTRUCTION NOT WOOD TO WOOD CONSTRUCTION. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- SHEET S-02:
 A) THE COMPONENT & CLADDING INFORMATION SHOWN ON THE
 MIDDLE OF THE SHEET IS INCORRECT. SEE TABLE R301.2(2)
 OF FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 B)DETAIL S-8: REVISE THE SIZE OF THE STRUCTURAL BUCK.
 STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE
 DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 6-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL).
  
 A)FLAT ROOF AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B) SKYLIGHT AS SHOWN ON PLANS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  