| 2019-06-07 19:14:05 | RESIDENTIAL(R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | SEC. 801.3 FBC-EXISTING BUILDING. |
| | |
| | 1- PROVIDE COMPLETE ENERGY CALCULATIONS (2 COPIES) AS |
| | REQUIRED BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. |
| | NOTE: COORDINATE WITH PLANS (SEE ENERGY CODE NOTES ON |
| | SHEET A-01) AND PRODUCT APPROVALS SUBMITTED TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2- SHEET A-01: |
| | A) REVISE THE WIND DESIGN DATA SHOWN UNDER THE CODE |
| | INFORMATION. THE CITY ULTIMATE DESIGN WIND SPEED IS 170 |
| | MPH AND THE CORRESPONDING NOMINAL DESIGN WIND SPEED IS |
| | 132 MPH. SEC. 120 CITY AMENDMENTS AND TABLE R301.2.1.3 |
| | FBC-RESIDENTIAL. |
| | |
| | B)REVISE THE WIND ZONE INFORMATION SHOWN UNDER THE CODE |
| | INFORMATION. INFORMATION GIVEN "WIND ZONE 4: BASIC WIND |
| | SPEED > 160MPH" IS INCORRECT. SEE SEC. R301.2.1.2.1 |
| | FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| | |
| | C)REVISE THE CODE INFORMATION REFERENCED ON THE TOP |
| | RIGHT CORNER OF THE SHEET. THE CURRENT BUILDING CODE IS |
| | THE 6TH EDITION NOT THE 5TH EDITION. NOTE: THIS COMMENT |
| | APPLIES TO ALL SHEETS. |
| | CHAPTER 553 F.S. |
| | |
| | 3- SHEET A-02: |
| | A)CLARIFY IF THE DESIGN PRESSURES SHOWN ON THE EXTERIOR |
| | ELEVATIONS FOR THE DOORS AND WINDOWS ARE THE ULTIMATE |
| | OR NOMINAL DESIGN PRESSURES. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE ICC EVALUATION REPORT (OR ANY OTHER APPROVED |
| | EVALUATION REPORT) FOR THE CLOSED CELL SPRAY FOAM |
| | INSULATION SPECIFIED ON THE MIDDLE OF THE SHEET FOR THE |
| | UNVENTED ATTIC. TO SHOW COMPLIANCE WITH THE |
| | REQUIREMENTS OF SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: COORDINATE R VALUE TO AVOID CONFLICTS/DELAYS. |
| | SPECIFICATIONS IN THIS SHEET CALL FOR R-40 SPRAY FOAM |
| | INSULATION, WHILE SPECIFICATIONS ON SHEET A-01 AND |
| | OTHER DETAILS ON SHEET S-01 CALL FOR R-30. COORDINATE |
| | TO MATCH. |
| | |
| | C) UPDATE THE PRODUCT APPROVALS NUMBERS SHOWN ON THE |
| | EXTERIOR DOOR & WINDOW SCHEDULE. THEY DON'T MATCH THE |
| | CURRENT PRODUCT APPROVALS SUBMITTED. |
| | FAC 61G20.3.001. |
| | |
| | 4- SHEET S-01: |
| | A) PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| | SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC. |
| | R703.1.2.1 FBC-RESIDENTIAL. |
| | ALSO, PROVIDE COMPLETE SPECIFICATIONS FOR THE FASCIA, |
| | INCLUDING ATTACHMENT. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | B) NEED TO SPECIFY RING SHANK NAILS ON ALL DETAILS ON |
| | THIS SHEET PROVIDING SPECIFICATIONS FOR THE ROOF |
| | SHEATHING AS REQUIRED BY SEC. R803.2.3.1 |
| | FBC-RESIDENTIAL. |
| | |
| | C)DETAIL S-7: NEED TO REVISE CONNECTOR SPECIFIED FOR |
| | CONNECTION BETWEEN DOUBLE TOP PLATES AND ROOF JOIST. |
| | SIMPSON H16 IS A CONNECTOR TO BE USED IN MASONRY |
| | CONSTRUCTION NOT WOOD TO WOOD CONSTRUCTION. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- SHEET S-02: |
| | A) THE COMPONENT & CLADDING INFORMATION SHOWN ON THE |
| | MIDDLE OF THE SHEET IS INCORRECT. SEE TABLE R301.2(2) |
| | OF FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| | |
| | B)DETAIL S-8: REVISE THE SIZE OF THE STRUCTURAL BUCK. |
| | STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE |
| | DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 6-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL). |
| | |
| | A)FLAT ROOF AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | B) SKYLIGHT AS SHOWN ON PLANS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |