2019-07-03 17:06:33****CORRECTIONS****
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ORIGINAL COMMENT:
 1. FBC R 301, PROVIDE SIMPSON PRODUCT APPROVAL FOR THE
 STRAP PROPOSED.
  
 RESPONSE:
 PRODUCT APPROVAL FOR REVISED STRAP WAS NOT PROVIDED.
  
 ORIGINAL COMMENT:
 2. ANDRE H. THOMAS, P.E. LETTER NEEDS TO BE REVISED
 AGAIN BECAUSE OF THE FOLLOWING:
 A) BASED ON SIMPSON PRODUCT APPROVAL SUBMITTED. THE
 SIMPSON H8 STRAP IS DESIGNED FOR WOOD TO WOOD
 CONNECTIONS. ACCORDING TO CITY RECORDS AND PALM BEACH
 COUNTY PROPERTY APPRAISER THE CONSTRUCTION OF THIS
 HOUSE IS CONCRETE BLOCK WALL WITH STUCCO NOT WOOD FRAME
 CONSTRUCTION. THEREFORE, ENGINEER NEEDS TO REVISE THE
 CONNECTOR. NEED TO SPECIFY A CONNECTOR THAT IS SUITABLE
 FOR THE EXISTING CONDITIONS. OR ENGINEER TO PROVIDE
 COMPLETE DETAILS AND ENGINEERING ANALYSIS SHOWING HOW
 THE H8 CONNECTOR WILL WORK (SEC. 107.2.1.2 CITY
 AMENDMENTS). NOTE: PLEASE DON'T SPECIFY "OR EQUIVALENT"
 WHEN SPECIFYING AN SPECIFIC CONNECTOR. THIS IS NOT
 ALLOWED BY SEC. 107.2.1 CITY AMENDMENTS.
 B) THE ENGINEER'S LETTER IS TOO GENERAL. ENGINEER NEEDS
 TO PROVIDE SITE SPECIFIC INFORMATION ABOUT THIS
 PROJECT. IDENTIFY WHAT ARE THE UPLIFT LOADS THAT NEED
 TO BE MET IN ORDER TO COMPLY WITH THE CURRENT BUILDING
 CODE REQUIREMENTS. PLEASE DO NOT CITE THE CODE AS A
 WHOLE OR IN PART (SEE SEC. 107.2.1 CITY AMENDMENTS).
 PROVIDE THE SITE SPECIFIC CALCULATIONS BASED ON THE
 TABLE REFERENCED ON THE LETTER SUBMITTED. SEC.
 107.2.1.2 CITY AMENDMENTS.
 C) ENGINEER TO BE SPECIFIC WITH THE CURRENT BUILDING
 CODE. SPECIFY THE CURRENT CODE EDITION. THE CURRENT
 BUILDING CODE ADOPTED BY THE CITY OF WEST PALM BEACH IS
 THE FBC SIXTH EDITION (2017).
 CHAPTER 553 F.S.
  
 RESPONSE:
 REVISED LETTER NEEDS TO BE REVISED AGAIN:
 A) ENGINEER NEEDS TO REVISE THE SPECIFIED CONNECTION.
 ENGINEER NEEDS TO READ FOOTNOTES "A" AND "B" OF
 REFERENCED TABLE 706.8.1 AND PROVIDE CONNECTION
 SPECIFICATIONS THAT WILL SATISFY THE TOTAL UPLIFT. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 B) ENGINEER TO CLARIFY CONNECTION AT THE GABLE ENDS.
 ENGINEER IS OMITTING CONNECTIONS AT THE GABLE ENDS.
 CLARIFY/REVISE AS REQUIRED. WHAT IS THE ENGINEER
 PROPOSING ABOUT THE UPLIFT AND LATERAL LOADS ON THE
 GABLE ENDS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 C) ENGINEER STATES THAT THE SCOPE OF WORK IS TO REMOVE
 THE EXISTING SOFFIT TO INSTALL THE STRAPS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE NEW
 SOFFIT WILL BE RE-BUILT. SEC. 706.8.1.1 FBC-EXISTING
 BUILDING AND SEC. R301.2.1 FBC-RESIDENTIAL.
  
 D) ENGINEER STATES THAT "IT APPEARS THE ROOF TRUSSES
 ARE NOT CONNECTED AT THE EXTERIOR CONCRETE WALLS AND
 COULD UTILIZE ADDITIONAL SUPPORT TO TIE IT DOWN". THIS
 STATEMENT IS CONTRADICTORY. IF IT DOESN'T HAVE A TIE
 DOWN, THEN THERE IS NO ADDITIONAL SUPPORT. ON THE OTHER
 HAND, THIS HOUSE WAS BUILT IN 1969. TYPICALLY, ROOF
 TRUSSES ARE CONNECTED TO THE WALL. THIS STATEMENT NEEDS
 SOME CLARIFICATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3. BASED ON THE PROPOSED SCOPE OF WORK, THE VALUATION
 DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION OR PROVIDE COPY OF SIGNED CONTRACTS AND
 INCLUDE DESIGN PROFESSIONAL FEES.
  
 RESPONSE:
 REPEAT COMMENT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  