2019-05-28 07:47:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, PROVIDE SIMPSON PRODUCT APPROVAL FOR THE
 H8 STRAP PROPOSED.
  
 2. THE ENGINEER'S LETTER STATES "PLEASE ACCEPT THIS
 LETTER OF RECOMMENDATION TO FULFILL THE REQUIREMENTS
 FOR THE PROPERTY OWNER TO MEET CURRENT BUILDING CODES".
 PLEASE REVISE TO BE MORE SPECIFIC (ADDRESS ROOF UPLIFT
 SUPPORT ONLY, SPECIFY BUILDING CODE).
  
 3. THE CONTRACTOR'S PLAN DOES NOT PROPOSE TO INSTALL
 STRAPS THROUGHOUT THE ENTIRE ROOF. ENGINEER IS TO DO A
 SHOP DRAWING REVIEW OF THE PLAN AND TO PROVIDE
 EXPLANATION AS TO WHY THIS PORTION IS NOT BEING DONE.
  