| Plan Review Notes For Permit 19050884 |
| Permit Number |
19050884 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-28 07:47:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, PROVIDE SIMPSON PRODUCT APPROVAL FOR THE | | | H8 STRAP PROPOSED. | | | | | | 2. THE ENGINEER'S LETTER STATES "PLEASE ACCEPT THIS | | | LETTER OF RECOMMENDATION TO FULFILL THE REQUIREMENTS | | | FOR THE PROPERTY OWNER TO MEET CURRENT BUILDING CODES". | | | PLEASE REVISE TO BE MORE SPECIFIC (ADDRESS ROOF UPLIFT | | | SUPPORT ONLY, SPECIFY BUILDING CODE). | | | | | | 3. THE CONTRACTOR'S PLAN DOES NOT PROPOSE TO INSTALL | | | STRAPS THROUGHOUT THE ENTIRE ROOF. ENGINEER IS TO DO A | | | SHOP DRAWING REVIEW OF THE PLAN AND TO PROVIDE | | | EXPLANATION AS TO WHY THIS PORTION IS NOT BEING DONE. | | | |
|