| 2019-07-01 08:50:28 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19050879 PRIME PERMIT: 19010578 |
| | ADD: 2717 POINSETTIA AVE. |
| | CONT: DILO FIRE SPRINKLERS |
| | TEL: 561-748-7255 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 01/2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET FP-1 UNDER THE HEADING OF SCOPE OF WORK AND |
| | GENERAL NOTE # 1 BOTH INDICATE THE INSTALLATION OF A |
| | PARTIAL FIRE SPRINKLER SYSTEM IN A CONGREGATE CARE |
| | FACILITY. IN THE TITLE BLOCK THE USE OF THIS BUILDING |
| | 1ST FLOOR A BIRTHING CENTER AND THE 2ND FLOOR AN R-3 |
| | SINGLE FAMILY RESIDENCE. PLEASE CORRECT. 107.2.1.2. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THE FIRE CHIEFS QUESTION AS TO WHY ONLY A PORTION OF |
| | THE 1ST FLOOR IS BEING FIRE SPRINKLERED. THE DESIGNER |
| | OF RECORD SHOULD PROVIDE A LETTER ON THEIR LETTERHEAD |
| | EXPLAINING WHY. THE 2ND FLOOR OCCUPANCY IS A SINGLE R-3 |
| | DWELLING UNIT. BEING IN A MIXED USE BUILDING THE |
| | FLORIDA BUILDING CODE- BUILDING CODE IS USED. IN A |
| | MIXED USE BUILDING UNDER THE 2017 FBC-B SECTION |
| | 903.2.8.1 WILL REQUIRE AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 903.3.1.3 WHICH IS A NFPA 13D SPRINKLER |
| | SYSTEM. |
| | |
| | THE SECOND FLOOR HAS ONLY ONE MEANS OF EGRESS PLUS THE |
| | REQUIRED EGRESS WINDOWS. THE CODE 2017 FBC-B TABLE |
| | 707.3.10 ALSO REQUIRES A 2 HR. FLOOR / CEILING |
| | ASSEMBLY. THERE IS ALSO RADIANT CEILING DAMPERS WITHIN |
| | THE FLOOR /CEILING ASSEMBLY UNDER THE R-3 PORTION OF |
| | THE BUILDING, WHERE FIRE ALARMS DEVICES ARE ALSO |
| | INSTALLED AS WELL AS THE STAIRWELL AND SECOND STORY |
| | LIVING QUARTERS. |
| | |
| | WE TOOK THIS CASE TO THE BUILDING OFFICIAL ASKING HIM |
| | THE CODE REALLY DOESN?T STATE WHERE THE R-13D |
| | SPRINKLERS ARE TO BE INSTALLED IN THE 2ND STORY PORTION |
| | OF THE BUILDING OR IN THE FIRE RATED FLOOR/ CEILING |
| | ASSEMBLY? HE AGREED IT WOULD MAKE MORE SINCE TO INSTALL |
| | THE SPRINKLERS IN THE 2ND FLOOR/CEILING ASSEMBLY TO |
| | HELP PROTECT THE 2 HOUR FIRE RATED ASSEMBLY. |
| | |
| | A LETTER WITH SIMILAR NARRATIVE SHOULD BE SUBMITTED |
| | FROM THE DESIGN PROFESSIONAL. PLEASE ALSO NOTE THE NFPA |
| | 13D FOUND IN THE 2017 FBC-B SECTION 903.3.13 STATES THE |
| | SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 13 D. |
| | NFPA 13D SECTION 6.5 DEALS WITH COMMON SUPPLY PIPES |
| | WHERE SERVE BOTH FIRE SPRINKLERS AND DOMESTIC USE, THEY |
| | SHALL COMPLY WITH 6.5.2 AND 6.5.3. |
| | |
| | 6.5.2 IN COMMON WATER SUPPLY CONECTIONS SERVING MORE |
| | THAN ONE DWELLING UNIT, 5 GPM SHALL BE ADDED TO THE |
| | FIRE SPRINKLER DEMAND TO DETERMINE THE SIZE OF COMMON |
| | PIPING AND THE SIZEE OF TOTAL WATER SUPPLY REQUIREMENTS |
| | WHERE NO PROVISIONS IS MADE TO PREVENT FLOW INTO |
| | DOMESTIC WATER SYSTEM UPON OPERATION OF A SPRINKLER. |
| | |
| | 6.5.3. WHERE WATER TREATMENT AND FILTRATION ARE |
| | INSTALLED, ON OF THE FOLLOWING CONDITIONS SHALL BE MET: |
| | (1). THE FLOW RESTRICTION AND PRESSUREE LOSS THROUGH |
| | THE WATER TREATMENT EQUIPMENT SHALL BE TAKEN INTO |
| | ACCOUNT IN THE HYDROLIC CALCULATIONS. |
| | (2). AN AUTOMATIC BYPASS SHALL BE INSTALLED AROUND THE |
| | WATER TREATEMENT EQUIPMENT THAT DIRECTS ALL WATER |
| | DIRECTLY TO THE SYSTEM. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |