| Date |
Text |
| 2019-08-04 10:08:59 | 1) TWO DIFFERENT DETAILS HAVE BEEN SUBMITTED FOR THE |
| | ENCLOSURE OF THE GAS LINE THROUGH THE STAIRWELL.ONE |
| | DETAIL IS SIGNED AND SEALED BY AN ARCHITECT AND SHOWS A |
| | RATED SOFFIT AND ANOTHER IS DONE BY BUCKEYE PLUMBING |
| | SHOWING BASICALLY A RATED BOX BEAM. I HAVE NO IDEA |
| | WHICH DETAIL IS TO BE USED. THE DETAIL TO BE USED SHALL |
| | BE SIGNED AND SEALED BY AN ARCHITECT. THE |
| | ENCLOSURE/SOFFIT SHALL HAVE A MINIMUM FIRE RESISTAVE |
| | RATING OF 2 HOURS. 2017 FBC SEC. 1023.2. |
| | 2) INDICATE THE SPACING OF THE STUDS ON THE DETAIL FOR |
| | THE SOFFIT. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) THE PLANS DONE BY THE ARCHITECT SHOW AN EXISTING |
| | RAIN WATER LEADER IN THIS SAME STAIRWELL. THIS MAY ALSO |
| | NEED TO BE ADDRESSED. |
| | 4) SHOW THE SOFFIT DIMENSIONS ( LXWXH) ON THE DRAWING |
| | BY MNA ARCHITECTS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 5) THE DRAWING BY MNA ARCHITECTS DOES NOTE THE REQUIRED |
| | 2 HOUR FIRE RESISTANCE RATING OF THE SOFFIT.THIS MUST |
| | BE NOTED ON THE PLANS. |
| | 6) SHOW THE CLEAR HEIGHT DIMENSION FROM THE FLOOR TO |
| | THE BOTTOM OF THE SOFFIT. THE DISTANCE SHALL BE NOT |
| | LESS THAN 7 FEET 6 INCHES PER 2017 FBC SEC.1003.2. |
| | 7) SUBMIT THE LISTED FIRE SAFING ASSEMBLY DETAILS FOR |
| | SEALING THE PIPE PENETRATIONS THROUGH THE STAIR AND THE |
| | SOFFIT.2017 FBC SEC. 714. |
| | 8) JOINTS IN THE LAYERED WALLBOARD SHALL BE STAGGERED |
| | IN RELATION TO LAYERS BELOW. |
| | 9) INDICATE ON THE PLANS HOW THE METAL TRACK STUDS WILL |
| | BE ATTACHED TO THE CONCRETE. SHOW TYPE, LENGTH, |
| | DIAMETER AND SPACING OF FASTENERS ON THE PLANS. |
| | 10) A BUILDING PERMIT WILL BE REQUIRED FOR THE SOFFIT |
| | BY A BUILDING CONTRACTOR AND ALSO A FIRE SPRINKLER |
| | PERMIT FOR THE WORK BEING DONE TO THE EXISTING FIRE |
| | LINE BY A CATEGORY I OR II FIRE PROTECTION CONTRACTOR. |
| | . |
| | 11) THE DETAIL FROM BUCKEYE NOTES THE BOX BEAM TO BE |
| | SELF SUSPENDED. THIS WILL HAVE TO BE VERIFIED BY AN |
| | ARCHITECT DUE TO THE LENGTH OF THE BEAM AND WEIGHT OF |
| | THE MATERIAL ATTACHED IF THIS DESIGN IS TO BE USED. |
| | 12) THE DETAIL FROM BUCKEYE SHALL SPECIFY THE TYPE OF |
| | SCREWS TO BE USED.WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | NOTE: PLEASE CALL THIS REVIEWER TO DISCUSS THESE |
| | COMMENTS BEFORE REBSUBMITTING. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |