Plan Review Notes
Plan Review Notes For Permit 19050865
Permit Number 19050865
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-11 16:05:57PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DETAIL FOR SHOWER PAN.
 P2709.1 SHOWER PAN CONSTRUCTION.
 P2709.3 SHOWER PAN LINING INSTALLATION.
  
 2. ONLY BATHROOM GOUPS LOCATED ON THE SAME FLOOR LEVEL
 ARE PERMITTED TO BE VENTED BY THE SAME HORIZONTAL WET
 VENT. 2ND FLOOR BATHROOM GROUP, KITCHEN SINK AND
 DISHWASHER MUST BE CONNECTED DOWNSTREAM OF THE FIRST
 FLOOR BATHROOM GROUP AND AHEAD OF THE BUILDING SEWER
 CLEANOUT.
 P3108.1HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO
 BE VENTED BY A HORIZONTAL WET VENT.
  
 3. EXHAUST FAN IS MISSING FROM BATHROOM # 203.
 R303.3BATHROOMS.
  
 4. THE WATER SHUT OFF VALVES SHALL BE ACCESSIBLE AT THE
 STACKABLE WASHER/DRYER.
 P2903.9.3FIXTURE VALVES AND ACCESS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  