| 2019-07-11 16:05:57 | PLUMBING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE DETAIL FOR SHOWER PAN. |
| | P2709.1 SHOWER PAN CONSTRUCTION. |
| | P2709.3 SHOWER PAN LINING INSTALLATION. |
| | |
| | 2. ONLY BATHROOM GOUPS LOCATED ON THE SAME FLOOR LEVEL |
| | ARE PERMITTED TO BE VENTED BY THE SAME HORIZONTAL WET |
| | VENT. 2ND FLOOR BATHROOM GROUP, KITCHEN SINK AND |
| | DISHWASHER MUST BE CONNECTED DOWNSTREAM OF THE FIRST |
| | FLOOR BATHROOM GROUP AND AHEAD OF THE BUILDING SEWER |
| | CLEANOUT. |
| | P3108.1HORIZONTAL WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO |
| | BE VENTED BY A HORIZONTAL WET VENT. |
| | |
| | 3. EXHAUST FAN IS MISSING FROM BATHROOM # 203. |
| | R303.3BATHROOMS. |
| | |
| | 4. THE WATER SHUT OFF VALVES SHALL BE ACCESSIBLE AT THE |
| | STACKABLE WASHER/DRYER. |
| | P2903.9.3FIXTURE VALVES AND ACCESS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |