| 2019-07-11 11:23:01 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE A.I.C. RATING OF TRANSFORMER FROM UTILITY |
| | COMPANY. |
| | |
| | SERVICE & METER |
| | FPL ELECTRIC SERVICE STANDARDS ? SECTION IV, A., 1. |
| | GENERAL. PG 1 OF 24 |
| | |
| | E3404.2INTERRUPTING RATING. |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS |
| | SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 |
| | AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT |
| | LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT |
| | LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9) |
| | |
| | 2. SEE PLAN PAGE E-1.01. ONE OF TWO CONDENSING UNITS IS |
| | MISSING. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. AHU2A & 2B MISSING FROM PANEL SCHEDULE. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. TANKLESS WATER HEATER MISSING FROM PANEL SCHEDULE. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. GFCI OUTLET REQUIRED AT EXTERIOR OF RESIDENCE. WEST |
| | ELEVATION. |
| | FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY |
| | DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE |
| | RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT |
| | MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | |
| | 6. OUTLET SPACING IN BEDROOM 204 APPEARS TO EXCEED THE |
| | 6 FT. MAX. FROM DOOR OPENING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. |
| | PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1 |
| | |
| | 7. OUTLETS MISSING IN N.E & S.E CORNERS OF ROOM 102. |
| | E3901.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |