2019-07-01 16:23:33ADDRESS: 205 PILGRIM RD PERMIT # 19050865
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. AN ELEVATION CERTIFICATE HAS BEEN INCLUDED IN THIS
 SUBMITTAL. THIS STRUCTURE IS NOT LOCATED IN A SPECIAL
 FLOOD HAZARD AREA (SFHA) WITH NO DESIGNATED FLOOD ZONE.
 PLEASE REMOVE THE ELEVATION CERTIFICATE FROM THIS
 SUBMITTAL.
  
 2. PROVIDE DESIGN PRESSURES FOR EACH WINDOW AND EXT.
 DOOR OPENING. YOU MAY PLACE THESE VALUES ON THE WINDOW
 AND DOOR SCHEDULE OR PLACE THEM ON THE PLANS NEXT TO
 EACH CORRESPONDING OPENING.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 3. ALL PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 4. PROVIDE SHOP DRAWINGS FOR PROPOSED ELEVATOR. NOT
 APPLICLABLE
  
 5. OWNER/AGENT SHALL SIGN THE ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. DESIGNER SHALL SELECT PRODUCT TO BE INSTALLED FROM
 THE ICYNENE INSTALLATION INSTRUCTIONS. COMPLIED SEE
 A-5.01
  
 7. PROPOSED GENERATOR REQUIRES SEPERATE PERMIT.
  
 8. PROPOSED GAS LINE REQUIRES SEPERATE PERMIT.
  
 9. DESIGNER TO SELECT PRODUCT TO BE INSTALLED FROM
 ROOFING NOA.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  