Plan Review Notes
Plan Review Notes For Permit 19050849
Permit Number 19050849
Review Stop P
Sequence Number 2
Notes
Date Text
2019-09-18 15:03:461) SUBMIT TWO COPIES OF ENERGY CODE CALCULATIONS THAT
 SHOW THE EF RATING OF THE WATER HEATER AS .96.
 2) SHT. P-1 - WATER HEATER SCHEDULE SHOWS THE EF RATING
 OF THE WATER HEATER AS .90. THE EF RATING SHALL BE A
 MINIMUM OF .96.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  