| Plan Review Notes For Permit 19050849 |
| Permit Number |
19050849 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-22 15:55:34 | PLUMBING 1ST REVIEW**DENIED** | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | 1) ENERGY EFFICIENCY FORM SHOULD BE 2017 NOT 2014 AS | | | PROVIDED. ALSO THE WATER HEATER EF OF .90 IS BELOW MIN | | | FEDERAL STANDARD. THE MIN IS .96 EF OR .93 U.E.F PER | | | FEDERAL REGISTER VOL 81, NO 250 POSTED ON 12/29/2016. | | | FBC-ENGERY C101.4.2.1 | | | | | | 2) THE WASHING MACHINE IS SHOWN TO BE VENTED BE AN AAV | | | DEVICE. AAV ARE ONLY PERMITTED ON WASHING MACHINES WHEN | | | THE HORIZONTAL BRANCH IS MIN 3". SEE STUDOR VENT | | | INSTALLATION MANUAL PAGE 19. | | | | | | 3) PLEASE ADD NOTED TO P-01 THAT ALL HOT WATER PIPING | | | OUTSIDE OF THE CONDITIONED SPACED SHALL BE INSULATED | | | WITH A MIN R-3 INSULATION. FBC-ENERGY R403.5.3 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] |
|