2019-05-22 15:55:34PLUMBING 1ST REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 1) ENERGY EFFICIENCY FORM SHOULD BE 2017 NOT 2014 AS
 PROVIDED. ALSO THE WATER HEATER EF OF .90 IS BELOW MIN
 FEDERAL STANDARD. THE MIN IS .96 EF OR .93 U.E.F PER
 FEDERAL REGISTER VOL 81, NO 250 POSTED ON 12/29/2016.
 FBC-ENGERY C101.4.2.1
  
 2) THE WASHING MACHINE IS SHOWN TO BE VENTED BE AN AAV
 DEVICE. AAV ARE ONLY PERMITTED ON WASHING MACHINES WHEN
 THE HORIZONTAL BRANCH IS MIN 3". SEE STUDOR VENT
 INSTALLATION MANUAL PAGE 19.
  
 3) PLEASE ADD NOTED TO P-01 THAT ALL HOT WATER PIPING
 OUTSIDE OF THE CONDITIONED SPACED SHALL BE INSULATED
 WITH A MIN R-3 INSULATION. FBC-ENERGY R403.5.3
  
  