Plan Review Notes
Plan Review Notes For Permit 19050849
Permit Number 19050849
Review Stop E
Sequence Number 1
Notes
Date Text
2019-06-04 10:52:24ADDRESS: 346 NOTTINGHAM BLVD. TYPE: BLD-RES NEW SFR
  
 ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 2. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4.
  
 3. REFERENCE PLAN PAGE E-1. NOTES USES THE WORD TEMPER
 WHEN NREFERING TO TAMPER RESISTANT RECEPTACLES. PLEASE
 CORRECT.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. OUTLET SPACING IN KITCHEN NOT PER CODE.
 THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER SPACE
 STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901.4
  
 5. GFCI OUTLET REQUIRED FOR DISHWASHER.
 PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D);
 FBC RE E3902.10.
  
 6. OUTLET SPACING FOR KITCHEN PENINSULA NOT PER CODE.
 E3901.4.3 PENINSULAR COUNTERTOP SPACE.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH PENINSULAR COUNTERTOP SPACE WITH A LONG DIMENSION
 OF 24 INCHES (610 MM) OR GREATER AND A SHORT DIMENSION
 OF 12 INCHES (305 MM) OR GREATER. A PENINSULAR
 COUNTERTOP IS MEASURED FROM THE CONNECTING EDGE.
 [210.52(C)(3)]
  
 7. IDENTIFY ALL GFCI PROTECTED OUTLETS.
 SECTION E3902
 GROUND-FAULT AND ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION
  
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10.E3902.10 KITCHEN DISHWASHER
 BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
  
 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 10. SMOKE DETECTORS SHALL BE SMOKE/CO COMBINATION
 DEVICES.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
 R314.5 COMBINATION ALARMS.
 COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE
 PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS.
  
 11. PROVIDE SERVICE OUTLET AT EXTERIOR MECHANICAL
 EQUIPMENT.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 12 . PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF
 THE LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES
 SHALL BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT
 OF THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  