| 2019-05-20 10:39:40 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING PLAN REVIEW DENIED: | | | | | | 1. FBC B 602.2 TYPE I AND TYPE II CONSTRUCTION IS TO BE | | | NON-COMBUSTIBLE; PAGE S-1 SHOWS COMBUSTIBLE MATERIAL IN | | | FLOORING MATERIAL INCLUDING FRAMING MEMBERS. | | | 2. FBC B 107.2.1 PROVIDE MORE DETAILS AND CALCULATIONS | | | FOR FLOOR FRAMING CONNECTIONS; CONNECTION DETAILS ON | | | PAGE S-1 APPEAR TO BE INCOMPLETE FOR SUPPORTING LOADS | | | ON WOOD FRAMED LANDING. | | | 3. FBC B 107.2.1 PROVIDE MORE DETAILS FOR CONNECTION OF | | | HANDRAILS TO WOOD LANDING; CONNECTION DETAILS FROM PAGE | | | S-1 APPEAR TO BE INCOMPLETE. | | | 4. FBC B 107.1 PROVIDE MANUFACTURER'S ENGINEERED | | | INSTALLATION SPECIFICATIONS INCLUDING CALCULATIONS | | | APPROVED BY THE ENGINEER OF RECORD. |
|