| Plan Review Notes For Permit 19050775 |
| Permit Number |
19050775 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-05-20 15:20:40 | PLUMBING 1ST REVISION REVIEW**DENIED** | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | 1) PROVIDE MAKE UP AIR FOR THE FIRE PLACE AND RANGE AS | | | THE BTU'S HAVE INCREASED FROM EXISTING . 2017 FBC-FUEL | | | GAS SEC.304.9.3 OR FBCR G2407.9.3. | | | | | | 2) PROVIDE TANKLESS WATER HEATER AND GAS VENT PIPE | | | INSTALLATION MANUAL. FBC 107.2.1 | | | | | | 3) PROVIDE DISTANCE THAT THE TANKLESS VENT PIPING IS | | | AWAY FROM ANY DOOR OR WINDOW THAT OPEN AND AWAY FROM | | | ANY MECHANICAL MAKE UP AIR VENT. FBC 107.2.1 | | | | | | | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|