| Plan Review Notes For Permit 19050721 |
| Permit Number |
19050721 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-06-03 14:49:13 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) A SURVEY OF THE PROPERTY WAS NOT PROVIDED WITH THE | | | PERMIT SUBMITTAL. PLEASE PROVIDE. | | | | | | 2.) WILL A WALKWAY FROM THE SIDEWALK TO THE COVERED | | | ENTRANCE BE PROVIDED? IF SO, PLEASE ILLUSTRATE IN THE | | | SITE PLAN. | | | | | | 3.) STRUCTURAL OVERHANGS (I.E. EAVES, ROOF OVERHANGS, | | | ETC.) SHALL NOT EXTEND MORE THAN 3 FT. INTO ANY | | | REQUIRED SETBACK. PLEASE SHOW DIMENSIONS FOR COMPLIANCE | | | WITH THIS REQUIREMENT. [ZLDR S.94-305(B)(2)] | | | | | | 4.) SHOW SETBACK DISTANCE FROM THE PROPOSED A/C UNIT | | | COMPRESSOR PAD TO THE PROPERTY LINE. PLEASE NOTE THAT | | | ALL MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 | | | FT. INTO A REQUIRED SETBACK. SHOW SETBACK DISTANCE FOR | | | CONSISTENCY. [ZLDR S.94-305(B)(4)] | | | | | | 5.) BUILDING ELEVATIONS DO NOT SEEM TO MATCH FLOOR PLAN | | | (I.E. DIRECTION). PLEASE ADDRESS FOR CONSISTENCY. | | | | | | 6.) A SEPARATE PERMIT FOR LANDSCAPING IS REQUIRED PRIOR | | | TO THE APPROVAL OF THIS PERMIT. PLEASE SUBMIT. | | | | | | NOTES: | | | | | | * SEPARATE PERMITS AND REVIEWS REQUIRED FOR: | | | LANDSCAPING AND HARDSCAPES (I.E. DRIVEWAY AND WALKWAYS, | | | PATIOS, ETC.). | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 |
|