| 2019-05-21 15:53:36 | PLUMBING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE A CODE COMPLIANT RISER DIAGRAHM. |
| | PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION |
| | 107.3.5.3 (12) |
| | |
| | 2. PROVIDE PAN FOR WATER HEATER. |
| | P2801.6REQUIRED PAN. |
| | WHERE A STORAGE TANK-TYPE WATER HEATER OR A HOT WATER |
| | STORAGE TANK IS INSTALLED IN A LOCATION WHERE WATER |
| | LEAKAGE FROM THE TANK WILL CAUSE DAMAGE, THE TANK SHALL |
| | BE INSTALLED IN A PAN CONSTRUCTED OF ONE OF THE |
| | FOLLOWING: |
| | 1. 1.GALVANIZED STEEL OR ALUMINUM OF NOT LESS THAN |
| | 0.0236 INCH (0.6010 MM) IN THICKNESS. |
| | 2. 2.PLASTIC NOT LESS THAN 0.036 INCH (0.9 MM) IN |
| | THICKNESS. |
| | 3. 3.OTHER APPROVED MATERIALS. |
| | |
| | 3. PROVIDE DETAIL FOR WATER HEATER DISCHARGE. |
| | P2804.6.1REQUIREMENTS FOR DISCHARGE PIPE. |
| | THE DISCHARGE PIPING SERVING A PRESSURE-RELIEF VALVE, |
| | TEMPERATURE RELIEF VALVE OR COMBINATION VALVE SHALL: |
| | DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER |
| | HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE |
| | OUTDOORS. |
| | P2801.6.2PAN DRAIN TERMINATION. |
| | THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER |
| | A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR SHALL |
| | EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE |
| | NOT LESS THAN 6 INCHES (152 MM) AND NOT MORE THAN 24 |
| | INCHES (610 MM) ABOVE THE ADJACENT GROUND SURFACE. |
| | |
| | 4. PROVIDE DETAIL FOR SHOWER PAN. |
| | P2709.1 SHOWER PAN CONSTRUCTION. |
| | P2709.3 SHOWER PAN LINING INSTALLATION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |