| 2019-05-21 12:31:04 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1. VALUE HAS BEEN ADJUSTED FROM $105,000 TO $129,257 |
| | BASED ON THE ICC BUILDING VALUATION DATA PUBLISHED FEB. |
| | 2019. |
| | |
| | 2. PROVIDE SITE DRAINAGE PLAN. |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| | COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| | |
| | 3. ROOFING PERMIT REQUIRED. NOA 14-1030.01 FOR FLAT |
| | ROOF HAS EXPIRED. PROVIDE NOA FOR PITCHED ROOF. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| | |
| | 4. PRODUCT APPROVALS FOR PROPOSED EXTERIOR DOORS IS |
| | PENDING. PROVIDE CURRENT APPROVED PRODUCT APPROVALS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE DOOR SUBMITTALS. |
| | |
| | 5. PROVIDE CONNECTION DETAIL BETWEEN CONTAINER AND |
| | FOUNDATION METAL PLATE EMBEDS. IF THIS IS A WELDED |
| | CONNECTION, PROVIDE WELD DETAILS. ALSO PROVIDE ON-SITE |
| | WELDER CERTIFICATIONS AT TIME OF INSPECTION. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PROVIDE CONNECTION DETAIL BETWEEN CONTAINERS. IF |
| | THIS IS A WELDED CONNECTION, PROVIDE WELD DETAILS. ALSO |
| | PROVIDE ON-SITE WELDER CERTIFICATIONS AT TIME OF |
| | INSPECTION. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. PROVIDE FASTNER SCHEDULE FOR EXTERIOR HIGH RIB METAL |
| | LATH TO CONTAINER. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. PROVIDE GUTTERS. |
| | R318.5PROTECTION AGAINST DECAY AND TERMITES. |
| | GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS |
| | WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL |
| | PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| | ABOVE ANOTHER ROOF. |
| | |
| | 9. PROVIDE PRODUCT SPECIFICATIONS FOR SPRAY FOAM |
| | INSULATION. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10. REF. PLAN PAGE S-1. THERE ARE TWO DETAILS MARKED 4. |
| | PLEASE CLARIFY. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 11. PROVIDE FRAMING DETAIL FOR ALL WINDOW AND EXTERIOR |
| | DOOR OPENINGS. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 12. REF. PLAN PAGE A-2 FOR THE FOLLOWING: |
| | 12A. SPECIFY SIZE OF ROOF RAFTERS. |
| | 12B. SPECIFY FASTENERS FOR 2X6 PT PLATE TO CONTAINER |
| | TOP RAIL. |
| | 12C. SPECIFY BOLTS AT H33 TO RAFTER CONNECTION. |
| | 12D. SOLID BLOCKING IS REQUIRED BETWEEN 2X6 TOP PLATE |
| | AND TOP OF CONTAINER. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 13. FOUNDATION PLAN PAGE S-1 SHOWS C2 COLUMN PADS IN |
| | INTERIOR OF FLOOR SPACE. DETAIL 2 PLAN PAGE A-2 SHOWS |
| | 16X16 CONTINUOS GRADE BEAMS. PLEASE CLARIFY. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. PROVIDE DETAIL FOR TOP OF POST CONNECTION FOR C2 |
| | COLUMN. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED OR MARK VOID. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |