| 2019-09-12 13:11:02 | 1) THE COVER SHEET FROM HKD DESIGN FOR THE CHARBROILER |
| | MODEL JBKC-36 SHOWS THE BTU CAPACITY AS 65.0 MBTU AND |
| | PAGE 2 OF THE SPECIFICATION SHEET LISTS THE BTU |
| | CAPACITY OF THEAT MODEL AS 90 MBTU. THE GAS RISER ON |
| | SHT.P2.1.1 SHOWS THE CAPACITY AS 130 MBTU. THE GAS LOAD |
| | SUMMARY TABLE ON SHT. P1.1.2. ALSO SHOWS 130 MBTU. |
| | CLARIFY. |
| | 2) THE COVER SHEET FROM HKD DESIGN FOR THE GAS FRYER |
| | MODEL SR142G LISTS ONE GAS FRYER AT 105 MBTU BUT THE |
| | GAS RISER NOTES 2 GAS FRYERS. IS IT ONE OR TWO? THE GAS |
| | LOAD SUMMARY TABLE ON SHT. P1.1.2 LISTS ONLY ONE FRYER. |
| | CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) THE COVER SHEET FROM HKD DESIGN FOR THE 36 INCH HD |
| | RANGE MODEL JTRH-36 IP-36 SHOWS THE BTU CAPACITY AS 70 |
| | MBTU AND SHT. 2 OF THE SPECIFICATIONS SHOWS 70 MBTU BUT |
| | THE GAS RISER SHOWS THE MBTU AS 35 . THE GAS LOAD |
| | SUMMARY ON SHT.P1.1.2 ALSO SHOWS THE MBTUH AS 35. THE |
| | GAS RISER AND THE GAS LOAD SUMMARY TABLE ONLY LIST ONE |
| | UNIT. CLARIFY |
| | 4) THE SUBMITTED SPECIFICATIONS FOR THE PASTA COOKER |
| | SHOW THE BTU CAPACITY AS 105 MBTU AND 140 MBTU.THE GAS |
| | RISER ON SHT. P2.1.1 AND GAS LOAD SUMMARY TABLE ON SHT. |
| | P1.1.2 SHOW THE MBTU CAPACITY AS 45. INDICATE ON THE |
| | SPECIFICATIONS WHICH MODEL OF THIS APPLIANCE IS USED |
| | AND REVISE THE CORRECT BTU CAPACITY ON THE GAS RISER |
| | AND GAS LOAD SUMMARY TABLE. |
| | 5) THE COVER SHEET FROM HKD DESIGN FOR THE 48 INCH |
| | RANGE MODEL JBR-8-36 AND THE SPECIFICATION SHEET SHOWS |
| | THE BTU CAPACITY AS 270 MBTU. THE GAS RISER ON SHT. |
| | P2.1.1 DOES NOT SHOW THIS APPLIANCE AND THE GAS LOAD |
| | SUMMARY TABLE ON SHT. P1.1.2 DOES NOT LIST THIS |
| | EQUIPMENT AT ALL. CLARIFY. |
| | 6) SPECIFICATIONS HAVE BEEN SUBMITTED FOR A SECTIONAL |
| | RANGE STOCK POT APPLIANCE.THIS APPLIANCE IS NOT SHOWN |
| | ON THE GAS RISER BUT IS LISTED IN THE GAS LOAD SUMMARY |
| | TABLE.ON SHT. P1.1.2. INDICATE THE MODEL NUMBER AND |
| | CORRESPONDING BTU LOAD OF THE APPLIANCE ON THE |
| | SPECIFICATION SHEETS. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) THE TOTAL BTU LOAD THAT IS SHOWN ON THE GAS RISER ON |
| | SHT. P2.1.1 MUST MATCH THE TOTAL BTU LOAD THAT IS SHOWN |
| | ON THE GAS LOAD SUMMARY TABLE ON SHT. P1.1.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |