| 2019-06-13 08:21:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19050696 |
| | 6/13/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-201: THE EXHAUST VENT FOR THE MED GAS ROOM |
| | IS MISLABELED AS THE GENERATOR EXHAUST FLUE- PLEASE |
| | CORRECT- SECTION 107.2.1 WPB. |
| | |
| | 2) M-201: PLACE DIMENSIONS OR NOTES ON THE PLAN |
| | VERIFYING THE REQUIRED 10' CLEARANCES FOR THE GENERATOR |
| | EXHAUST FLUE, THE GENERATOR RADIATOR EXHAUST DISCHARGE, |
| | AND THE MED GAS EXHAST VENTS TO A) OPERABLE OPENINGS |
| | AND MECHANICAL AIR INTAKES INTO THE BUILDING B) |
| | ADJOINING GRADE C) PROPERTY LINES- SECTION 501.3.1 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |