| 2019-09-18 10:38:04 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19050683 |
| | REVIEWED: JULY 19, 2019 |
| | 2 ND REVIEW: SEPTEMBER 18, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | ADDITIONAL COMMENT: |
| | IN REVIEWING THE GEOTECHNICAL REPORT IT APPEARS THAT |
| | THE RECOMMENDATIONS ARE NOT BEING IMPLEMENTED (SEE PAGE |
| | 6 OF 14 IN GEO REPORT). |
| | ALSO, SEE CODE REQUIRMENTS FOR DEPTH OF FOOTING. |
| | 1809.4 FBC[B] DEPTH AND WIDTH OF FOOTINGS. THE MINIMUM |
| | DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE |
| | SHALL BE 12 INCHES. WHERE APPLICABLE, THE REQUIREMENTS |
| | OF SECTION. |
| | FOOTER IS SHOWN AT 18 DEEP, BUT IT SHOWS ONLY 8 INCHES |
| | BELOW GRADE. |
| | PLEASE REVIEW FOOTER GRADE DEPTH AND PROVIDE RESPONSE |
| | FOR WHAT IS THE DEPTH OF FOOTER INTO GRADE. |
| | |
| | PROVISOS: |
| | - NO RESPONSE REQUIRED. THESE WILL BE ADDED TO THE |
| | PLANS AT FINAL STAMPING. |
| | |
| | 1. PROVIDE PRODUCT APPROVALS FOR WINDOWS, STOREFRONT |
| | AND DOORS. |
| | 2. ROOF TRUSS SHOP DRAWINGS TO BE PROVIDED TO THE |
| | INSPECTOR PRIOR TO INSTALLATION. |
| | 3. PROVIDE PRODUCT APPROVALS AND ENGINEERING, IF |
| | APPLICABLE, WITH SUB PERMIT APPLICATION FOR FLAT ROOF. |
| | 4. SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS AS |
| | WELL. AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE |
| | SPRINKLERS, LOW VOLTAGE, LANDSCAPING, PARKING LOT AND |
| | SITE LIGHTING |
| | 5. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | |
| | IF THERE ARE MORE DEFFERED SUBMITTALS THAN LISTED |
| | ABOVE, PLEASE PUT IN A RESPONSE AND I WILL ADD THEM TO |
| | FINAL LIST. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |