| 2019-07-18 15:23:51 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | 1. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR KITCHEN EQUIPMENT PER FBC FG 304.1 |
| | 2. P201 |
| | A. GAS ISOMETRIC |
| | 1) PER WPB FBC 107.2.1, ISOMETRIC DRAWING SHALL CLEARLY |
| | SHOW THE LENGTH OF ALL CUT SECTIONS OF PIPE AND CONFIRM |
| | THAT SIZING IS IN ACCORDANCE WITH FBC PL 402.4.1, |
| | 402.4.2. |
| | 2) PROVIDE UNION BETWEEN MANUAL VALVE AND THE AUTOMATIC |
| | SHUT OFF VALVE FOR THE EMERGENCY SHUT DOWN TO THE |
| | COOKING LINE PER NFPA 96, SECS. 10.4, 10.5. |
| | B. NOTE 1: PER WPB FBC 107.2.1, PROVIDE A SPECIFICATION |
| | FOR FLEXIBLE GAS CONNECTORS COMPLYING WITH FBC FG |
| | 411.1. |
| | 3. P301 |
| | A. P301 WATER HEATER DETAIL; RESEARCH OF THE CONCENTRIC |
| | VENT SEEMS TO INDICATE THAT THIS PRODUCT IS FOR |
| | SIDEWALL INSTALLATION ONLY. PER WPB FBC 107.2.1, |
| | PROVIDE MANUFACTURER AND MODEL # FOR CONCENTRIC VENT |
| | WITH DOCUMENTATION THAT ALLOWS VERTICAL INSTALLATION |
| | FOR ROOF PENETRATION AND IS NOT LIMITED TO SIDEWALL |
| | INSTALLATION. IF SIDEWALL INSTALLATION IS TO BE USED |
| | THEN PROVIDE LOCATION ON BUILDING WALL AND INCLUDE AN |
| | ELEVATION DETAIL SHOWING COMPLIANCE WITH FBC FG 502 |
| | THROUGH 505. IF THROUGH THE ROOF VENTING IS TO BE USED |
| | THEN PROVIDE A DETAIL FOR THAT INSTALLATION SHOWING |
| | COMPLIANCE WITH FBC FG 502 THROUGH 505. EITHER DETAIL |
| | SHALL SHOW TYPE, LOCATION, SIZE, TERMINATION POINT, |
| | HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS |
| | VENT(S) AS ARE APPLICABLE. |
| | B. DETAIL 3 SHOWS GAS PIPING ABOVE ROOF. FLOOR PLAN |
| | SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE |
| | CLARIFY PER WPB FBC 107.2.1. |
| | C. DETAIL 10 SHOWS GAS PIPING TO ABOVE ROOF. FLOOR PLAN |
| | SHOWS PIPING BELOW ROOF ABOVE THE CEILING. PLEASE |
| | CLARIFY PER WPB FBC 107.2.1. |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE |
| | WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |