| 2019-07-19 16:04:38 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 19050683 |
| | REVIEWED: JULY 19, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 401.2 FBC[CE] |
| | THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| | SECTION 9.4.1.1(G) OF THE STANDARD. |
| | -PLEASE ADJUST THE DOOR SECTION TO MEET WHAT IS |
| | PROVIDED IN THE PLANS. CURRENTLY THE ENERGY CALCS SHOW |
| | SOLID CORE DOORS ON N, E AND S SIDES. |
| | PLANS SHOW GLASS DOORS ON THE N AND W SIDES AND |
| | MULTIPLE HOLLOW METAL ON THE S SIDE. |
| | - ALSO, THE ROOF SECTION STATES METAL ROOF, BUT THE |
| | PLANS SHOW WOOD TRUSSES WITH PLYWOOD. COORDINATE THE |
| | PLANS WITH THE ENERGY CALCS. |
| | |
| | 2) SHEET A503 DETAIL 12 SHOWS R-19 BATTS AT THE 1 5/8 |
| | METAL FURRING. THAT DOES NOT MATCH THE ENERGY |
| | CALCULATION STHAT CALL FOR 6.9 AT THE MASONRY WALLS. |
| | ENERGY CALC AT 6.9 SEEMS TO BE THE CORRECT R VALUE. |
| | A) PLEASE CO-ORDINATE THE ENERGY CALS AND PLANS. |
| | ALSO, THERE IS A BREAK IN THERMAL ENVELOPE BETWEEN THE |
| | TOP OF 1 5/8 METAL FURRING AND THE ROOF SUSPENDED R39 |
| | BATT INSULATION. PLEASE SHOW ON PLANS HOW THERMAL |
| | ENVELOPE IS |
| | B) SHOW ON PLANS HOW THERMAL ENVELOPE IS MAINTAINED. |
| | |
| | 3) PLEASE PROVIDE BASE FLOOD ELEVATION CERTIFICATE FEMA |
| | FORM 086-0-33 TO SHOW WHAT PROPOSED BASE ELEVATION IS |
| | GOING TO BE. |
| | - DUE TO THE PROXIMITY OF THE BUILDING TO AE FLOOD ZONE |
| | , A BASE FLOOD ELEVATION CERTIFICATE WILL BE NEEDED TO |
| | DOCUMENT THAT THE FINISHED FLOOR ELEVATION MEETS THE |
| | BFE 12.7 NAVD PLUS 2 FOOT FREEBOARD ESTABLISHED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 4) 110.3(A)1.1 FBC[AMENDED] A FOUNDATION/FORM BOARD |
| | SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR |
| | MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB |
| | INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE |
| | BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING |
| | SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB |
| | SITE FOR REVIEW BY THE BUILDING INSPECTOR. |
| | PROVIDE BASE FLOOD ELEVATION(B.F.E.) IN CERTIFICATE |
| | WITH DESIGN FLOOD ELEVATIONS TO INCLUDE ANY MECHANICAL |
| | EQUIPMENT AS APPLICABLE. ALL ELEVATION CERTIFICATES |
| | CERTIFIED OCTOBER 5, 2017 AND LATER ARE TO UTILIZE |
| | NAVD88 AND INCLUDE A CONVERSION TO NGVD29. |
| | |
| | 5) 602.3 TYPE III CONSTRUCTION. |
| | - PLEASE CONVEY THAT THIS CONSTRUCTION TYPE REQUIRES |
| | TWO HOUR EXTERIOR WALL AND THE EXECPTION IN NOTE A |
| | WOULD APPLY TO REDUSE IT TO ONE HOUR. |
| | |
| | 6) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING |
| | CAPACITY AND FOUNDATION RECOMMENDATIONS. |
| | -ADD MULTI PAGE PDF TO SUPPORTING DOCUMENT IN PROJECT |
| | DOX. |
| | |
| | 7) [FBC 107.5][FBC 110.9][FBC R401.3][THE CIVIL PLANS |
| | PROVIDED ARE BASED IN NGVD 29. THE CITY OF WEST PALM |
| | BEACH HAS BEEN UTILZING NAVD 88. |
| | - PLEASE PROVIDE CIVIL PLAN ELEVATIONS IN NAVD, OR |
| | PROVIDE CONVERSION SO THAT ELEVATION CERTIFICATE CIVIL |
| | PLANS CAN BE COMPARED WITH PROPER CONVENTION. |
| | |
| | 8) 1803.5.8 FBC[B] COMPACTED FILL MATERIAL. WHERE |
| | SHALLOW FOUNDATIONS WILL BEAR ON COMPACTED FILL |
| | MATERIAL MORE THAN 12 INCHES (305 MM) IN DEPTH, A |
| | GEOTECHNICAL INVESTIGATION SHALL BE CONDUCTED AND SHALL |
| | INCLUDE ALL OF THE FOLLOWING: |
| | - (SEE 1803.5.8 FOR REQUIREMENTS) |
| | |
| | 9) 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER |
| | ASSEMBLIES. |
| | - IS THE CEILING SPACE VENTED? |
| | |
| | 10) 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED |
| | INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE |
| | INSTALLED IN ACCORDANCE WITH ITEM 5.1. IN ADDITION TO |
| | THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW |
| | THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET |
| | INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE |
| | STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE R |
| | VALUES IN TABLE 1203.3 FOR CONDENSATION CONTROL. |
| | - REVIEW THIS SECTION FOR AIR PERMEABLE INSULATION IN |
| | REGARDS TO CONDENSATION CONTROL. |
| | |
| | 11) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT |
| | I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A |
| | LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND. |
| | SOME ITEMS ON THE LIST MAY INCLUDE: STOREFRONT, DOORS, |
| | ROOFING, WOOD TRUSSES. |
| | |
| | 11A) SEPARATE PERMITS WILL BE REQUIRED FOR SOME ITEMS |
| | AS WELL. |
| | - AWNINGS, TRASH ENCLOSURE, FIRE ALARM, FIRE |
| | SPRINKLERS, LOW VOLTAGE , LANDSCAPING, PARKING LOT AND |
| | SITE LIGHTING |
| | |
| | 12) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | FOR WINDOWS, STOREFRONT AND DOORS. |
| | - OR PUT IN THE DEFERRED SUBMITTAL LIST. |
| | |
| | 13) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS. |
| | PLEASE PROVIDE FOR FLAT ROOF. |
| | - OR PUT IN THE DEFERRED SUBMITTAL LIST. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |