| 2019-05-22 13:14:07 | 5/22/19 |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET T 1.1 - THERE IS AN INDICATION OF AN INCORRECT |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE; 3RD. |
| | |
| | THE CURRENT EDITION OF THE FFPC IS THE 6TH. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEETS ASP 1.0 & C 2.0 - THERE IS AN INDICATION OF A |
| | PASS THRU LANE WITH A WIDTH DIMENSION OF 13'6" FROM |
| | CURB TO CANOPY EDGE WITH A HEIGHT OF 9'6". |
| | |
| | FIRE DEPARTMENT ACCESS AROUND THE BUILDING REQUIRES A |
| | WIDTH OF 20' AND HEIGHT OF 13'6". |
| | |
| | THE EXISTING PARKING AREA ACCOMODATED FIRE DEPARTMENT |
| | 20'; HOWEVER, THE DEMO C 1.2 PLAN REMOVES IT. |
| | |
| | PER NFPA 1, CH 18 |
| | |
| | 18.2.3.2 ACCESS TO BUILDING. |
| | |
| | 18.2.3.2.1 A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND |
| | TO WITHIN 50 FT |
| | (15 M) OF AT LEAST ONE EXTERIOR DOOR THAT CAN BE OPENED |
| | FROM THE |
| | OUTSIDE AND THAT PROVIDES ACCESS TO THE INTERIOR OF THE |
| | BUILDING. |
| | |
| | 18.2.3.4 SPECIFICATIONS. |
| | 18.2.3.4.1 DIMENSIONS. |
| | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED |
| | WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| | 18.2.3.4.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED |
| | VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1 |
| | M). |
| | 18.2.3.4.1.2.1 VERTICAL CLEARANCE SHALL BE PERMITTED TO |
| | BE REDUCED, |
| | PROVIDED SUCH REDUCTION DOES NOT IMPAIR ACCESS BY FIRE |
| | APPARATUS, AND |
| | APPROVED SIGNS ARE INSTALLED AND MAINTAINED INDICATING |
| | THE ESTABLISHED |
| | VERTICAL CLEARANCE WHEN APPROVED. |
| | 18.2.3.4.1.2.2 VERTICAL CLEARANCES OR WIDTHS SHALL BE |
| | INCREASED WHEN |
| | VERTICAL CLEARANCES OR WIDTHS ARE NOT ADEQUATE TO |
| | ACCOMMODATE FIRE |
| | APPARATUS. |
| | |
| | PLEASE REVIEW AND CORRECT RAODWAY WIDTH/CANOPY HEIGHT |
| | AND/OR PROVIDE DIMENSIONS FROM EDGE OF EAST PARKING LOT |
| | TO FRONT ENTRANCE DOOR MEETING THE ABOVE50 FT. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |