| 2019-05-16 09:16:02 | 1ST REVIEW: 19050677 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLAN SHEETS SHALL BE SIGNED AND SEALED BY ENGINEER |
| | LISTED ON TOP OF TITLE BLOCK LUIS C MAURY. PER FAC |
| | 61G15-23.003 |
| | |
| | 2. VALUATION FOR THIS JOB APPEARS TO BE LOW PLEASE |
| | PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR BONA |
| | FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO MEET |
| | THE |
| | APPROVAL OF THE BUILDING OFFICIAL. PER WPB AMEND TO FBC |
| | 109.3 |
| | |
| | 3. SHT A1 THE PROPOSED FLOOR PLAN SHOWS AN EXISTING |
| | WATER HEATER SHT E1 SHOWS A NEW TANKLESS AND THE |
| | EXISTING TANK TYPE WATER HEATER IS THE OLD HEATER |
| | REMAINING IN USE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. PLEASE PROVIDE DIMENSIONS OF THE SHOWER SHALL COMPLY |
| | WITH FBC RES P2708.1 |
| | |
| | 5. PLEASE SHOW CLEANOUT ON THE ISOMETRIC DRAWING WERE |
| | THE NEW BUILDING DRAIN EXISTS THE STRUCTURE. PER FBC |
| | RES P3005.2.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |