| Date |
Text |
| 2019-05-21 13:54:03 | 1ST REVIEW: 19050604 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1.SHT. A.08 DETAIL #6 IT APPEARS THE LAVATORY IS |
| | ENCROACHING INTO THE 60"X56" CLEAR FLOOR SPACE FOR THE |
| | TOILET.NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE |
| | LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. PER |
| | FBC ACC 604.3.2 |
| | |
| | 2. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR. |
| | |
| | 3. THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC |
| | A) 602.2 CLEAR FLOOR SPACE. UNITS SHALL HAVE A CLEAR |
| | FLOOR OR GROUND SPACE COMPLYING WITH 305 POSITIONED FOR |
| | A FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND |
| | TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | B)602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | C)602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. SPOUT |
| | OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS |
| | SHALL BE 38 INCHES MINIMUM AND 43 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | D)306.3.1 GENERAL. SPACE UNDER AN ELEMENT BETWEEN 9 |
| | INCHES AND 27 INCHES ABOVE THE FINISH FLOOR OR GROUND |
| | SHALL BE CONSIDERED KNEE CLEARANCE AND SHALL COMPLY |
| | WITH 306.3. |
| | E)306.2.1 GENERAL. SPACE UNDER AN ELEMENT BETWEEN THE |
| | FINISH FLOOR OR GROUND AND 9 INCHES ABOVE THE FINISH |
| | FLOOR OR GROUND SHALL BE CONSIDERED TOE CLEARANCE AND |
| | SHALL COMPLY WITH 306.2. |
| | |
| | 4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| | OF THE GRIPPING SURFACE,PER FBC ACC 609.4 |
| | |
| | 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.6 FLUSH |
| | CONTROLS. FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| | SIDE OF THE WATER CLOSET EXCEPT IN AMBULATORY |
| | ACCESSIBLE COMPARTMENTS COMPLYING WITH 604.8.2 |
| | |
| | 6.THE BREAK ROOM SINKS SHALL COMPLY WITH FBC ACC 606.2 |
| | CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND |
| | TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 7. IN THE NEW BATHROOM THERE IS A PLUMBING FIXTURE THAT |
| | THE ARCHITECTURAL SHEETS ARE CALLING A MOP SINK THE |
| | PLUMBING SHEET IS CALLING IT A SHOWER PLEASE CLARIFY IF |
| | IT IS A SHOWER IT SHALL COMPLY WITH FBC ACC 608.2.1 , |
| | 608.3.1 , 608.5.1 , 610.3 |
| | |
| | 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 9. BACKFLOW IS REQUIRED FOR THE ICE MACHINE IN |
| | REFRIGERATOR IF ONE PROVIDED. PER FBC PL 608.3 |
| | |
| | 10. THE WATER FOUNTAIN ON THE 2ND FLOOR SHALL CONNECT |
| | TO BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. |
| | PER FBC PL 912.1 |
| | |
| | 11. SHT. A.08 DETAIL #2 SHOWS A MOP SINK BUILT IN PLACE |
| | WITH LATICRETE HYDROBAN WATER PROOFING THE PLUMBING |
| | SCHEDULE IS LISTING P-5 PRE FAB SHOWER PLEASE |
| | CLARIFY.PER WPB AMEND TO FBC 107.2.1 |
| | |
| | . |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |