Plan Review Notes
Plan Review Notes For Permit 19050604
Permit Number 19050604
Review Stop M
Sequence Number 1
Notes
Date Text
2019-05-30 17:30:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050603
 5/30/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS- SECTION C403.2.1 FBC EC.
  
 2) SHOW THE LOCATIONS OF THE NEW AC CONDENSERS ON THE
 ROOF AND INDICATE HOW ACCESS WILL BE PROVIDED- SECTION
 107.2.1 WPB.
  
 3) SHEET M0.1: REFER TO SECTION 306.1 FBC M AND VERIFY
 THE NEW ACCESS PANELS WILL BE SIZED LARGE ENOUGH TO
 REPLACE THE ABOVE CEILING AIR HANDLERS- SECTION 306.1
 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved